Line 29: Line 29:
 
!Values
 
!Values
 
!Description
 
!Description
|-
 
 
|rowspan="2"|gui
 
|rowspan="2"|true
 
|true
 
|enable support for the UI object, UISET actions and USER commands
 
|-
 
|false
 
|disable UI support
 
 
|-
 
|-
  
Line 48: Line 39:
 
|start generating events only after HSYCO is aligned with the current status of the system
 
|start generating events only after HSYCO is aligned with the current status of the system
 
|-
 
|-
 
|unitid
 
|1
 
|> 0
 
|MODBUS unit ID of the KILSEN panel
 
  
 
|-
 
|-
  
|nodes
+
|pollinterval
|1
+
|1000
 
|
 
|
|nodes list. Multiple nodes should be separated by semicolons
+
|the data polling interval, in milliseconds. Shorter time improve the response of the system, but increase the load on the CPU of both HSYCO and the Xensity system
  
|-
 
  
|loopsnumber
 
|1
 
|> 0
 
|total number of loops
 
 
|-
 
 
|sensorsnsumber
 
|1
 
|style="white-space:nowrap"|0 ... 128
 
|set to the highest sensor number configured in the panel
 
|-
 
 
|modulesnumber
 
|1
 
|style="white-space:nowrap"|0 ... 128
 
|set to the highest module  number configured in the panel
 
 
|-
 
|-
  
 
|}
 
|}
 
  
 
== Datapoints ==
 
== Datapoints ==

Revision as of 10:24, 23 March 2020

DEA XENSITY is a Point ID intrusion detection system using special piezoelectric sensors for the protection of doors, windows, glass surfaces, security grilles and walls. This driver is compatible with the following controllers: Xensity128, Xensity64, Xensity32. Make sure to install the latest available firmware.

Communication

DEA XENSITY panels can be connected via ethernet. A valid IP address must be assigned to the controller using the configuration software.

Note  In case of multiple DEA XENSITY IO Servers running on the same HSYCO Server you must assign a different UDP port to each XENSITY driver

HSYCO Configuration

Add a XENSITY I/O Server in the I/O Servers section of the Settings and set its parameters:

Communication

  • Address: IP address of the XENSITY controller (mandatory)
  • Port: UDP port (mandatory)

High Availability

  • Shutdown when inactive: defaults to false.

Options

ID Default Values Description
startupevents false true generate IO events also during the driver’s start-up phase
false start generating events only after HSYCO is aligned with the current status of the system
pollinterval 1000 the data polling interval, in milliseconds. Shorter time improve the response of the system, but increase the load on the CPU of both HSYCO and the Xensity system


Datapoints

ID Value R/W Description
connection online R connection established
offline R HSYCO can't connect to the panel
reset 1 W panel reset
reset 1 W panel reset
panel.silence 1 W silence panel
sounders.set 0 W stop sounders
1 W start sounders
global.alarm 0 R no alarm
1 R at lest one sensor of module on alarm
global.fault 0 R no faults
1 R at lest one sensor of module on fault status
global.disable 0 R no sensors of modules disabled
1 R at lest one sensor of module is disabled
global.test 0 R panel in not in test mode
1 R panel is in test mode
global.daynight 0 R panel in day mode
1 R panel is night mode
global.mcpalarm 0 R mcp alarm off
1 R mcp alarm on
global.sounder.delay.enabled 0 R sounders delay disabled
1 R sounders delay enabled
global.sounder.delay.in.progress 0 R sounders delay not in progress
1 R sounders delay in progress
global.sounder.outputs.activated 0 R sounders outputs not active
1 R sounders outputs active
global.sounder.outputs.silenced 0 R sounders outputs not silenced
1 R sounders outputs silenced
global.sounder.disabled 0 R sounders are enabled
1 R sounders are disabled
global.sounder.override.time.elapsed 0 R override sounders time is not elapsed
1 R ovveride sounders time elapsed
global.sounder.in.test 0 R sounders not in test
1 R sounders in test
global.fire.routing.delay.enabled 0 R fire routing delay not enabled
1 R fire routing delay enabled
global.fire.routing.delay.in.progress 0 R fire routing delay not in progress
1 R fire routing in progress
global.fire.routing.ouputs.activated 0 R fire routing outputs not activated
1 R fire routing outputs activated
global.fire.routing.ack 0 R fire routing not in ack
1 R fire routing ack
global.fire.routing.disabled 0 R fire routing enabled
1 R fire routing disabled
global.fire.routing.test.on 0 R fire routing test is off
1 R fire routing test on
global.fire.routing.ext.delay.in.progress 0 R fire routing ext delay not in progress
1 R fire routing ext delay in progress
node.<n>.loop.<l>.sensor.<s>.prealarm 0 R not in prealarm
1 R prealarm
node.<n>.loop.<l>.sensor.<s>.alarm 0 R not in alarm
1 R alarm
node.<n>.loop.<l>.sensor.<s>.fault 0 R not in fault
1 R fault
node.<n>.loop.<l>.sensor.<s>.test 0 R not in test
1 R in test
node.<n>.loop.<l>.sensor.<s>.dis 0 R enabled
1 R disabled
node.<n>.loop.<l>.module.<s>.prealarm 0 R not in prealarm
1 R prealarm
node.<n>.loop.<l>.module.<s>.alarm 0 R not in alarm
1 R alarm
node.<n>.loop.<l>.module.<s>.fault 0 R not in fault
1 R fault
node.<n>.loop.<l>.module.<s>.test 0 R not in test
1 R in test
node.<n>.loop.<l>.module.<s>.dis 0 R enabled
1 R disabled

Release Notes

3.7.0

  • initial release