Difference between revisions of "TLABQ"

From HSYCO
Jump to navigation Jump to search
Line 634: Line 634:
 
|-
 
|-
  
|rowspan="15" |z<n>
+
|rowspan="2" |z<n>
|rowspan="15"|visible
+
|visible
 
|true
 
|true
 
|when datapoint with ID <datapoint_id> has value '0'
 
|when datapoint with ID <datapoint_id> has value '0'

Revision as of 12:06, 2 March 2021

The TLAB-Q is a multi-area security system

HSYCO Configuration

Add the TLABQ I/O Server in the I/O Servers section of the Settings and set its parameters:

Communication

  • IP Address: host name or IP address of the panel
  • IP Port: TCP/IP port assigned to the panel's web server

Authentication

  • User: username to access the web server
  • Password: password to access the web server

Options

ID Default Values Description
startupevents false true generate IO events also during the driver’s start-up phase
false start generating events only after HSYCO is aligned with the current status of the system
gui true true enable the UISET "visible" field for all system zones
false disable the UISET "visible" field for all system zones
pollinterval 1000 n > 1000 the data acquisition interval, in milliseconds
logsize 400 n ≥ 0 the number of log lines to display in the UI object


Datapoints

ID Value R/W Description
connection online R connection established
offline R HSYCO can't connect to the panel
id Q R security panel series identification
model Quadrio R security panel model
Small
Medium
Large
fw <text> R firmware version running on the security panel
dataconfig 0..999 R data configuration version
accesstype admin R connection established
no_valid_access R HSYCO can't connect to the panel
<user_index> R HSYCO can't connect to the panel
temp <val> R security panel temperature (C°)
credit <val> R SIM credit (€)
gsm.fault 1 R gsm error detected
0 R no gsm error
gsm.fault.cause 1 R network registration error
2 R no SIM
3 R no service provider
4 R low signal
5 R no response to sent command
6 R SIM pin block
pstn.fault 1 R PSTN fault detected
0 R no PSTN fault
nopower 1 R no power supply
0 R power supply in normal state
nopower.device 65534 R system detected lack of power supply
<n> R index of device that detected lack of power supply
batt.fault 1 R battery fault detected
0 R no battery fault
batt.fault.device 65534 R system detected battery fault
<n> R index of device that detected battery fault
tamper 1 R tamper on a device detected
0 R no tamper detected
tamper.device 65534 R system in tampering
<n> R index of device in tampering
coercion 1 R user coercion detected
0 R no user coercion detected
coercion.user <n> R index of user under duress
radiointerference 1 R radiointerference detected
0 R no radiointerference detected
radiozone.fault 1 R radio zone fault detected
0 R no radio zone fault detected
radiozone.fault.zone <n> R index of radio zone fault
theft 1 R theft detected
0 R no theft detected
theft.device <n> R index of device that detected theft
medemergency 1 R medical emergency detected
0 R no medical emergency detected
medemergency.device <n> R index of device that detected medical emergency
radiohooter.fault 1 R radio hooter fault detected
0 R no radio hooter fault detected
radiohooter.fault.device <n> R index of device that detected radio hooter fault
radiokeyboard.fault 1 R radio keyboard fault detected
0 R no radio keyboard fault detected
radiokeyboard.fault.device <n> R index of device that detected radio keyboard fault
radiohooter.ids <text> R list of radio hooter indexes in tampering
remoteaccess 1 R remote access detected
0 R no remote access detected
a<n>.name <text> R/W name of area <n> (max. 16 characters)
a<n>.ins 0 W disarm all groups in area <n>
1 W arm all groups in area <n>
a<n>.alarmgroups <text> R list of groups, in area <n>, in alarm state
a<n>.tampergroups <text> R list of groups, in area <n>, in tampering
a<n>.prealarmgroups <text> R list of groups, in area <n>, in pre-alarm state
a<n>.blindgroups <text> R list of groups, in area <n>, in blind state
a<n>.group.<a,b,c,d>.en 0 R group <a,b,c,d> in area <n> is disabled
1 R group <a,b,c,d> in area <n> is enabled
a<n>.group.<a,b,c,d>.ins 0 R/W group <a,b,c,d> in area <n> is disarmed
1 R/W group <a,b,c,d> in area <n> is armed
a<n>.group.<a,b,c,d>.name <text> R/W name of group <a,b,c,d> in area <n> (max. 16 characters)
totaloutputs <n> R total outputs number associated to the security panel
totalradiooutputs <n> R total radio outputs number associated to the security panel
o<n>.status 0 R output n doesn't exist
1 R output n not configured and disabled
2 R output n not configured and enabled
11 R output n configured and disabled
12 R output n configured and enabled
o<n> 0 W disable output n
1 W enable output n
o<n>.name <text> W change name of output n (max. 16 characters)
o<n>.sec 0 W remove timing on output n
<k> W output n will change status (enable/disable) after k seconds
totalwiredzones <n> R total wired zones number
totalradiozones <n> R total radio zones number
z<n>.status 0 R zone n not configured
1 R zone n excluded
2 R zone n in normal state
3 R zone n in tampering
11 R zone n open internal contact
12 R zone n open external contact
13 R zone n open internal and external contacts
20 R alarm memory in zone n and all contacts closed
21 R alarm memory in zone n and internal contact open
22 R alarm memory in zone n and external contact open
23 R alarm memory in zone n and all contact open
40 R zone n in alarm and all contacts closed
41 R zone n in alarm and internal contact open
42 R zone n in alarm and all external contact open
43 R zone n in alarm and all contacts open

User Interface

UISET Actions

ID Attribute Set to
log value latest security log lines (as many as specified by the 'logsize' option)
log0 value latest security log (it will vanish after 5 seconds)
z<n> visible true when datapoint with ID <datapoint_id> has value '0'
false when datapoint with ID <datapoint_id> has value '1'

Release Notes

3.8.0

  • initial release