Lares4
The KSENIA lares 4.0 is a multi-area security system. The I/O Server has been tested on unit with firmware version 1.72.2 and web server version 1.32.7. Actually this driver runs only in HTTP mode (port 80 is set by default).
Contents
HSYCO Configuration
Add a LARES4 I/O Server in the I/O Servers section of the Settings and set its parameters:
Communication
- IP Address: host name or IP address of the panel
- IP Port: leave it blank
Authentication
- Password: pin to access the web server
High Availability
- Shutdown when inactive: defaults to false.
Options
ID | Default | Values | Description |
---|---|---|---|
startupevents | false | true | generate IO events also during the driver’s start-up phase |
false | start generating events only after HSYCO is aligned with the current status of the system | ||
pollinterval | 1000 | n > 1000 | the data acquisition interval, in milliseconds |
logsize | 300 | n ≥ 0 | the number of log lines to display in the UI object |
gui | true | true | enable the UISET "visible" field for all partition zones |
false | disable the UISET "visible" field for all partition zones | ||
maxpartitions | 3 | 1≤n≤30 | number of partitions that are configured in the security panel |
Datapoints
ID | Value | R/W | Description |
---|---|---|---|
connection | online | R | connection established |
offline | R | HSYCO can't connect to the panel | |
armed | 1 | W | arm all partitions in the system |
0 | W | disarm all partitions in the system | |
p<n>.desc | <text> | R | description of partition <n> |
p<n>.armed | 0 | R | partition <n> is disarmed |
W | disarm partition <n> | ||
1 | R | partition <n> is armed | |
W | arm partition <n> | ||
p<n>.alarm | 0 | R | partition <n> not in alarm |
1 | R | partition <n> in alarm | |
p<n>.tamper | 0 | R | partition <n> not in tamper |
1 | R | partition <n> in tamper | |
z<n>.desc | <text> | R | description of zone <n> |
z<n>.alarm | 0 | R | zone <n> not in alarm |
1 | R | zone <n> in alarm | |
z<n>.mask | 0 | R | zone <n> not masked |
1 | R | zone <n> masked | |
z<n>.tamper | 0 | R | zone <n> not in tamper |
1 | R | zone <n> in tamper | |
z<n>.error | 0 | R | zone <n> not in error |
1 | R | zone <n> in error | |
z<n>.bypass | 0 | R | zone <n> is not bypassed |
W | unbypass zone <n> | ||
1 | R | zone <n> is bypassed | |
W | bypass zone <n> | ||
o<n>.desc | <text> | R | description of output <n> |
o<n> | 0 | R | output <n> is off |
W | turn off output <n> | ||
1 | R | output n <n> is on | |
W | turn on output <n> | ||
voltage.low | 0 | R | system voltage is ok |
1 | R | system voltage is low | |
batt.low | 0 | R | battery is ok |
1 | R | battery is low | |
batt.fault | 0 | R | battery is ok |
1 | R | battery fault | |
pstn.fault | 0 | R | pstn is ok |
1 | R | pstn fault | |
credit.low | 0 | R | credit is ok |
1 | R | credit is low | |
system.fault | 0 | R | system is ok |
1 | R | system fault | |
mobile.fault | 0 | R | mobile is ok |
1 | R | mobile fault | |
s<n>.desc | <text> | R | description of scenario <n> |
s<n> | 1 | W | trigger scenario <n> |
User Interface
UISET Actions
ID | Attribute | Set to | |
---|---|---|---|
log | value | latest security log lines (as many as specified by the 'logsize' option) | |
log0 | value | latest security log (it will vanish after 5 seconds) | |
z<n>.tamper | visible | false | zone n not in tampering |
true | zone n in tampering | ||
z<n>.bypass | visible | false | zone n not bypassed |
true | zone n bypassed | ||
z<n>.alarm | visible | false | zone n not in alarm |
true | zone n in alarm | ||
z<n>.error | visible | false | zone n not in error state |
true | zone n in error state | ||
z<n>.mask | visible | false | zone n not masked |
true | zone n masked |
Log Files
If a Ksenia anti-intrusion unit is connected to HSYCO, the security.log file will be written in the same directories as the daily log files.
This file is never overwritten or deleted from HSYCO SERVER.
2018.02.20 16:59:28.516 - lares - 20/02/2018 16:56:36 - Disinserimento - Part 1 - U1 2018.02.20 17:00:24.527 - lares - 20/02/2018 16:57:36 - Inserimento - Part 1 - U1 2018.02.20 17:00:44.318 - lares - 20/02/2018 16:57:57 - Allarme - Zone 1 2018.02.20 17:00:49.241 - lares - 20/02/2018 16:57:58 - Ripristino - Zone 1 2018.02.20 17:00:54.043 - lares - 20/02/2018 16:58:06 - Disinserimento - Part 1 - U1 2018.02.20 17:01:18.905 - lares - 20/02/2018 16:58:29 - Fallita Comunicazione - Leonardo - Vocale GSM 2018.02.20 17:01:29.053 - lares - 20/02/2018 16:58:40 - Fallita Comunicazione - Leonardo - SMS
Other information about the Ksenia driver are stored in the message.log daily file.
Release Notes
3.8.0
- initial version release