TSECMACS
The TSEC MACS MACS is a perimeter anti-intrusion system for rigid and semi-rigid metal fences.
HSYCO Configuration
Add the TSECMACS I/O Server in the I/O Servers section of the Settings and set its parameters:
Communication
- IP Address: host name or IP address of the panel
- IP Port: TCP/IP port assigned to the panel's web server
Authentication
- Username: username to access the web server
- Password: password to access the web server
Options
ID | Default | Values | Description |
---|---|---|---|
startupevents | false | true | generate IO events also during the driver’s start-up phase |
false | start generating events only after HSYCO is aligned with the current status of the system | ||
gui | false | true | |
false | |||
pollinterval | 1000 | n >= 1000 | the data acquisition interval, in milliseconds |
Datapoints
ID | Value | R/W | Description |
---|---|---|---|
connection | online | R | connection established |
offline | R | HSYCO can't connect to the sensor | |
sensor.<n>.isenabled | 1 | R | The sensor is enabled |
0 | R | The sensor is NOT enabled | |
rotation | <value> | R | sensor current rotation. Values around 0 mean the sensor is horizontal (volumetric) while values around 90 mean the sensor is vertical (barrier) |
totaltargets | n >= 0 | R | total targets detected by the sensor simultaneously |
targets.<n>.distance | <value> | R | distance in mm of target <n> from the sensor |
targets.<n>.rcs | <value> | R | measure of the size of detected target <n> |
targets.<n>.id | <value> | R | identifier of target <n>. The identifier may change if the target is lost |
totalarms | n >= 0 | R | total alarms triggered simultaneously |
alarms.<n>.detection | alarm | R | detection situation, alarm <n> has been triggered in the alarm area |
pre-alarm | R | detection situation, alarm <n> has been triggered in the pre-alarm area | |
alarms.<n>.tampering | moved | R | tampering situation with alarm <n>, the sensor has been moved |
masked | R | tampering situation with alarm <n>, the sensor has been masked | |
alarms.<n>.fault | voltage | R | fault situation with alarm <n>, input voltage out of range |
firmware | R | fault situation with alarm <n>, firmware internal error | |
HW-RF | R | fault situation with alarm <n>, hardware RF head | |
HW-MEMS | R | fault situation with alarm <n>, hardware MEMS | |
mask | R | fault situation with alarm <n>, masking not ready | |
storage | R | fault situation with alarm <n>, corrupted storage | |
motion | R | fault situation with alarm <n>, motion detector not responding | |
alarms.<n>.totaltargets | n >= 0 | R | total targets detected simultaneously, associated with alarm <n> |
alarms.<n>.targets.<m>.distance | <value> | R | distance in mm of target <m> (associated with alarm <n>) from the sensor |
alarms.<n>.targets.<m>.rcs | <value> | R | measure of the size of detected target <m> (associated with alarm <n>) |
alarms.<n>.targets.<m>.id | <value> | R | identifier of target <m> (associated with alarm <n>) |