EL.MO. ETR100 is a multi-area intrusion detection system. The integration with HSYCO can be accomplished via direct control through the RS232 port on the panel.
Communication
Employ the RS-232 cable provided with the EL.MO. panel to connect it directly to HSYCO or to an Ethernet/RS-232 gateway.
RS-232 parameters:
Baud rate
|
9600
|
Data bits
|
8
|
Stop bit
|
1
|
Parity
|
none
|
Flow control
|
none
|
Options
ID
|
Default
|
Values
|
Description
|
gui
|
true
|
true
|
enable automatic support of UI objects to show the system status and intercept control buttons
|
false
|
disable support for the UI
|
startupevents
|
false
|
true
|
generate IO events also during the driver’s start-up phase
|
false
|
start generating events only after HSYCO is aligned with the current status of the system
|
offlinelogs
|
true
|
false
|
at startup request the log of all the events occurred while HSYCO was disconnected from the panel
|
false
|
log only events occurred while HSYCO was connected to the panel
|
pollinterval
|
1
|
n > 0
|
the data acquisition interval, in seconds
|
logsize
|
20
|
n ≥ 0
|
the number of log lines to display in the UI object
|
Datapoints
ID
|
Value
|
R/W
|
Description
|
connection
|
online
|
R
|
connection established
|
offline
|
R
|
HSYCO can't connect to the panel
|
armed
|
1
|
R
|
at least one partition is armed
|
W
|
arm all active areas
|
0
|
R
|
no partition is armed
|
W
|
disarm all active areas
|
armed.max
|
1
|
R
|
at least one partition is armed in "max security" mode
|
W
|
arm all active areas in "max security" mode
|
0
|
R
|
no partition is armed in "max security" mode
|
W
|
disarm all active areas in "max security" mode
|
alarm
|
1
|
R
|
alarm state active
|
0
|
R
|
no active alarm
|
tamper
|
1
|
R
|
tamper alarm active
|
0
|
R
|
no active tamper alarm
|
i<n>.name
|
<text>
|
R
|
the name of input <n> is set to <text>
|
i<n>.open
|
1
|
R
|
input <n> open
|
0
|
R
|
input <n> closed
|
i<n>.alarm
|
1
|
R
|
alarm on input <n>
|
0
|
R
|
no alarm on input <n>
|
i<n>.tamper
|
1
|
R
|
tamper alarm on input <n>
|
0
|
R
|
no tamper alarm on input <n>
|
i<n>.bypassed
|
1
|
R
|
input <n> bypassed
|
W
|
bypass input <n>
|
0
|
R
|
input <n> enabled
|
W
|
enable input <n>
|
o<n>
|
1
|
R
|
output <n> active
|
W
|
activate output <n>
|
0
|
R
|
output <n> inactive
|
W
|
deactivate output <n>
|
a<n>.<m>.name
|
<text>
|
R
|
the name of partition <m> of area <n> is set to <text>
|
a<n>.armed
|
1
|
W
|
arm all partitions of area <n>
|
0
|
W
|
disarm all partitions of area <n>
|
a<n>.armed.max
|
1
|
W
|
arm all partitions of area <n> in "max security" mode
|
0
|
W
|
disarm all partitions of area <n> in "max security" mode
|
a<n>.<m>.armed
|
1
|
R
|
partition <m> of area <n> is armed
|
W
|
arm partition <m> of area <n>
|
0
|
R
|
partition <m> of area <n> is disarmed
|
W
|
disarm partition <m> of area <n>
|
a<n>.<m>.armed.max
|
1
|
R
|
partition <m> of area <n> is armed in "max security" mode
|
W
|
arm partition <m> of area <n> in "max security" mode
|
0
|
R
|
partition <m> of area <n> is not armed in "max security" mode
|
W
|
disarm partition <m> of area <n> in "max security" mode
|
usr<n>.name
|
<text>
|
R
|
the name of user <n> is set to <text>
|
kp<n>.tamper
|
1
|
R
|
keypad <n> tampered
|
0
|
R
|
keypad <n> not tampered
|
fault.battery
|
1
|
R
|
battery fault active
|
0
|
R
|
no battery fault active
|
panel.tamper
|
1
|
R
|
panel tampered
|
0
|
R
|
panel not tampered
|
rel.tamper
|
1
|
R
|
tamper relay is on
|
0
|
R
|
tamper relay is off
|
rel.alarm
|
1
|
R
|
alarm relay is on
|
0
|
R
|
alarm relay is off
|
User Interface
Object
Elmo (Object)
Display Objects
ID
|
Attribute
|
Set to
|
log
|
text
|
latest security log lines (as many as specified by the 'logsize' option)
|
log0
|
text
|
latest line of the security log when a new entry is added, set back to blank after a short period
|
i<n>.name
|
text
|
name assigned to input <n>
|
a<n>.<m>.name
|
text
|
name assigned to partition <m> of area <n>
|
usr<n>.name
|
text
|
name assigned to user <n>
|
connection.label
|
visible
|
true
|
when datapoint connection = offline
|
false
|
when datapoint connection = online
|
<datapoint_id>.label.1
|
visible
|
true
|
when datapoint with ID <datapoint_id> has value '1'
|
false
|
when datapoint with ID <datapoint_id> has value '0'
|
<datapoint_id>.label.0
|
visible
|
true
|
when datapoint with ID <datapoint_id> has value '0'
|
false
|
when datapoint with ID <datapoint_id> has value '1'
|
Command Objects
Name
|
Param
|
Action
|
armed
|
1
|
arm all active areas
|
0
|
disarm all active areas
|
armed.max
|
1
|
arm all active areas in "max security" mode
|
0
|
disarm all active areas in "max security" mode
|
ID.a<n>.armed
|
1
|
arm all partitions of area <n>
|
0
|
disarm all partitions of area <n>
|
a<n>.armed.max
|
1
|
arm all partitions of area <n> in "max security" mode
|
0
|
disarm all partitions of area <n> in "max security" mode
|
a<n>.<m>.armed
|
1
|
arm partition <m> of area <n>
|
0
|
disarm partition <m> of area <n>
|
a<n>.<m>.armed.max
|
1
|
arm partition <m> of area <n> in "max security" mode
|
0
|
disarm partition <m> of area <n> in "max security" mode
|
i<n>.bypassed
|
1
|
bypass input <n>
|
0
|
enable input <n>
|
o<n>
|
1
|
activate output <n>
|
0
|
deactivate output <n>
|