RACKPDU

From HSYCO
Jump to navigation Jump to search

The APC by Schneider Electric Rack Power Distribution Unit (PDU) may be used as a stand-alone, network- manageable power distribution device or up to four devices can be connected together using one network connection. The Rack PDU provides real-time remote monitoring of connected loads.

The HSYCO RACKPDU driver supports the AP88XX and AP78XXB Metered models.

IO Server RACKPDU.jpg

PDU Configuration

In order to be able to control the device with HSYCO SERVER, remote access to the command line interface via SSH must be enabled.

HSYCO Configuration

Add a RACKPDU I/O Server in the I/O Servers section of the Settings and set its parameters:

Communication

  • IP Address: the IP address of the device
  • IP Port: TCP/IP port to use (defaults to 22)
  • User: the SSH user (defaults to "apc")
  • Password: the SSH password (defaults to "apc").


High Availability

  • Shutdown when inactive: defaults to false.

Options

ID Default Values Description
startupevents false true generate IO events also during the driver’s start-up phase
false start generating events only after HSYCO is aligned with the current status of the system

Datapoints

All measured values returned as datapoints use the units as set in the PDU. The unit is not returned in the datapoint value.


ID Value R/W Description
connection online R connection established
offline R not connected to the PDU
bklowload <value> R bank low-load threshold current in amps
bknearover <value> R bank near-overload threshold current in amps
bkoverload <value> R bank overload threshold current in amps
devlowload <value> R low-load threshold in kilowatts for the device
devnearover <value> R near-overload threshold in kilowatts for the device
devoverload <value> R overload threshold in kilowatts for the device
humreading <value> R humidity value from the sensor (%RH)
phlowload <value> R phase low-load threshold (amps)
phnearover <value> R phase near-overload threshold (amps)
phoverload <value> R phase overload threshold (amps)
tempReading <value> R temperature value in Celsius
bkpeakcurr <value> R bank peak current measurement in amps
bkreading <value> R bank current reading (measurement) in amps
devpeakload <value> R peak power measurement in kilowatts from the device
devreading.power <value> R total power in kilowatts for the device
devreading.energy <value> R total energy in kilowatt-hours for the device
devreading.appower <value> R total apparent power in kilovolt amperes for the device
devreading.pf <value> R total power factor for the device
phpeakcurr <value> R peak current measurement from a phase (amps)
phreading.current <value> R measured current for a phase (amps)
phreading.voltage <value> R measured voltage for a phase (volts)
phreading.power <value> R measured power for a phase (watts)
phreading.appower <value> R measured apparent power for a phase (va)
phreading.pf <value> R measured power factor for a phase
hp <value> R hail peak intensity (hits/cm2h, hits/in2h, hits/ h)
th <value> R heating temperature (C, F)

Release Notes

3.6.0

  • initial version release