TLABQ
Jump to navigation
Jump to search
The TLAB-Q is a multi-area security system
Contents
HSYCO Configuration
Add the TLABQ I/O Server in the I/O Servers section of the Settings and set its parameters:
Communication
- IP Address: host name or IP address of the panel
- IP Port: TCP/IP port assigned to the panel's web server
Authentication
- User: username to access the web server
- Password: password to access the web server
Options
ID | Default | Values | Description |
---|---|---|---|
startupevents | false | true | generate IO events also during the driver’s start-up phase |
false | start generating events only after HSYCO is aligned with the current status of the system | ||
gui | true | true | enable the UISET "visible" field for all system zones |
false | disable the UISET "visible" field for all system zones | ||
pollinterval | 1000 | n > 1000 | the data acquisition interval, in milliseconds |
logsize | 400 | n ≥ 0 | the number of log lines to display in the UI object |
Datapoints
ID | Value | R/W | Description |
---|---|---|---|
connection | online | R | connection established |
offline | R | HSYCO can't connect to the panel |
User Interface
UISET Actions
ID | Attribute | Set to | |
---|---|---|---|
log | value | latest security log lines (as many as specified by the 'logsize' option) | |
connection.online | visible | true | when datapoint connection = online |
false | when datapoint connection = offline | ||
connection.offline | visible | true | when datapoint connection = offline |
false | when datapoint connection = online | ||
<datapoint_id>.1 | visible | true | when datapoint with ID <datapoint_id> has value '1' |
false | when datapoint with ID <datapoint_id> has value '0' | ||
<datapoint_id>.0 | visible | true | when datapoint with ID <datapoint_id> has value '0' |
false | when datapoint with ID <datapoint_id> has value '1' |
USER Commands
Name | Param | Action |
---|---|---|
p<n>.armed | 0 | disarm partition <n> |
1 | arm partition <n> | |
p<n>.armed.part | 1 | part arm partition <n> |
p<n>.reset | 1 | reset partition <n> |
o<n> | 0 | set PC controlled output <n> off |
1 | set PC controlled output <n> on | |
ox<n> | 0 | set X-10 controlled output <n> off |
1 | set X-10 controlled output <n> on | |
key | <code> | send keypad key (see above for codes) |
Release Notes
3.8.0
- initial release