The TSEC MACS MACS is a perimeter anti-intrusion system for rigid and semi-rigid metal fences.
HSYCO Configuration
Add the TSECMACS I/O Server in the I/O Servers section of the Settings and set its parameters:
Communication
- IP Address: host name or IP address of the panel
- IP Port: TCP/IP port assigned to the panel's web server
Authentication
- Username: username to access the web server
- Password: password to access the web server
Options
ID
|
Default
|
Values
|
Description
|
startupevents
|
false
|
true
|
generate IO events also during the driver’s start-up phase
|
false
|
start generating events only after HSYCO is aligned with the current status of the system
|
gui
|
false
|
true
|
|
false
|
|
pollinterval
|
1000
|
n >= 1000
|
the data acquisition interval, in milliseconds
|
Datapoints
Utility Datapoints
ID
|
Value
|
R/W
|
Description
|
connection
|
online
|
R
|
connection established
|
offline
|
R
|
HSYCO can't connect to the sensor
|
sensor.<n>.isenabled
|
1
|
R/W
|
The sensor is enabled
|
0
|
R/W
|
The sensor is NOT enabled
|
sensor.<n>.zoneid
|
<value>
|
R
|
Returns the zone id of the sensor
|
zone.<m>.name
|
<value>
|
R
|
Returns the zone name
|
zone.<m>.outputid
|
<value>
|
R
|
Returns the zone output id
|
Alarms Datapoints
Sensors
Zones
ID
|
Value
|
R/W
|
Description
|
alarm
|
0/1
|
R
|
This datapoint will return 1 if just one sensor or zone is in alarm
|
sensor.<n>.alarm.cumulative
|
0/1
|
R
|
Returns 1 if just one alarm is on for the requested sensor
|
sensor.<n>.alarm.accelerometer.fault
|
0/1
|
R
|
Accelerometer fault alarm
|
sensor.<n>.alarm.bus.fault
|
0/1
|
R
|
Bus fault alarm
|
sensor.<n>.alarm.climbing.alarm
|
0/1
|
R
|
Climbing alarm
|
sensor.<n>.alarm.climbing.prealarm
|
0/1
|
R
|
Climbing pre alarm
|
sensor.<n>.alarm.communication.mas-eth.lost
|
0/1
|
R
|
Communication to the mas-eth lost alarm
|
sensor.<n>.alarm.communication.security.problem
|
0/1
|
R
|
Generic communication security problem alarm
|
sensor.<n>.alarm.communication.with.sensor.failed
|
0/1
|
R
|
Communication with sensor failed alarm
|
sensor.<n>.alarm.configuration.in.progress
|
0/1
|
R
|
Configuration in progress alarm
|
sensor.<n>.alarm.consistency.error
|
0/1
|
R
|
Consistency error alarm
|
sensor.<n>.alarm.cut.alarm
|
0/1
|
R
|
Cut alarm
|
sensor.<n>.alarm.cut.prealarm
|
0/1
|
R
|
Cut pre alarm
|
sensor.<n>.alarm.error.writing.parameters.on.sensor
|
0/1
|
R
|
Error writing parameters on sensor alarm
|
sensor.<n>.alarm.magnetic.attack.alarm
|
0/1
|
R
|
Magnetic attack alarm
|
sensor.<n>.alarm.persistent.perturbation.alarm
|
0/1
|
R
|
Persistent perturbation alarm
|
sensor.<n>.alarm.persistent.perturbation.prealarm
|
0/1
|
R
|
Persistent perturbation pre alarm
|
sensor.<n>.alarm.power.supply.problems
|
0/1
|
R
|
Power supply problems alarm
|
sensor.<n>.alarm.remove.alarm
|
0/1
|
R
|
remove alarm
|
sensor.<n>.alarm.remove.alarm
|
0/1
|
R
|
Returns 1 if the alarm is removed
|
sensor.<n>.alarm.sd.card.not.inserted.or.damaged
|
0/1
|
R
|
SD card not inserted or damaged alarm
|
sensor.<n>.alarm.sensor.fault
|
0/1
|
R
|
Sensor fault alarm
|
sensor.<n>.alarm.sensor.not.found
|
0/1
|
R
|
Sensor not found alarm
|
sensor.<n>.alarm.sporadic.cut.alarm
|
0/1
|
R
|
Sporadic cut alarm
|
sensor.<n>.alarm.sporadic.cut.prealarm
|
0/1
|
R
|
Sporadic cut pre alarm
|
sensor.<n>.alarm.tamper.mas
|
0/1
|
R
|
Tamper mas alarm
|
sensor.<n>.zone.or.output.not.use
|
0/1
|
R
|
Zone or output not use alarm
|
ID
|
Value
|
R/W
|
Description
|
alarm
|
0/1
|
R
|
This datapoint will return 1 if just one sensor or zone is in alarm
|
zone.<n>.alarm.cumulative
|
0/1
|
R
|
Returns 1 if just one alarm is on for the requested zone
|
zone.<n>.alarm.accelerometer.fault
|
0/1
|
R
|
Accelerometer fault alarm
|
zone.<n>.alarm.bus.fault
|
0/1
|
R
|
Bus fault alarm
|
zone.<n>.alarm.climbing.alarm
|
0/1
|
R
|
Climbing alarm
|
zone.<n>.alarm.climbing.prealarm
|
0/1
|
R
|
Climbing pre alarm
|
zone.<n>.alarm.communication.mas-eth.lost
|
0/1
|
R
|
Communication to the mas-eth lost alarm
|
zone.<n>.alarm.communication.security.problem
|
0/1
|
R
|
Generic communication security problem alarm
|
zone.<n>.alarm.communication.with.sensor.failed
|
0/1
|
R
|
Communication with sensor failed alarm
|
zone.<n>.alarm.configuration.in.progress
|
0/1
|
R
|
Configuration in progress alarm
|
zone.<n>.alarm.consistency.error
|
0/1
|
R
|
Consistency error alarm
|
zone.<n>.alarm.cut.alarm
|
0/1
|
R
|
Cut alarm
|
zone.<n>.alarm.cut.prealarm
|
0/1
|
R
|
Cut pre alarm
|
zone.<n>.alarm.error.writing.parameters.on.sensor
|
0/1
|
R
|
Error writing parameters on sensor alarm
|
zone.<n>.alarm.magnetic.attack.alarm
|
0/1
|
R
|
Magnetic attack alarm
|
zone.<n>.alarm.persistent.perturbation.alarm
|
0/1
|
R
|
Persistent perturbation alarm
|
zone.<n>.alarm.persistent.perturbation.prealarm
|
0/1
|
R
|
Persistent perturbation pre alarm
|
zone.<n>.alarm.power.supply.problems
|
0/1
|
R
|
Power supply problems alarm
|
zone.<n>.alarm.remove.alarm
|
0/1
|
R
|
remove alarm
|
zone.<n>.alarm.remove.alarm
|
0/1
|
R
|
Returns 1 if the alarm is removed
|
zone.<n>.alarm.sd.card.not.inserted.or.damaged
|
0/1
|
R
|
SD card not inserted or damaged alarm
|
zone.<n>.alarm.sensor.fault
|
0/1
|
R
|
Sensor fault alarm
|
zone.<n>.alarm.sensor.not.found
|
0/1
|
R
|
Sensor not found alarm
|
zone.<n>.alarm.sporadic.cut.alarm
|
0/1
|
R
|
Sporadic cut alarm
|
zone.<n>.alarm.sporadic.cut.prealarm
|
0/1
|
R
|
Sporadic cut pre alarm
|
zone.<n>.alarm.tamper.mas
|
0/1
|
R
|
Tamper mas alarm
|
zone.<n>.zone.or.output.not.use
|
0/1
|
R
|
Zone or output not use alarm
|