INIM PREVIDIA are multi-zone fire panels. The integration with HSYCO can be accomplished via a standard Modbus TCP/IP connection. This I/O server was developed following the MODBUS documentation INIM Guida all'integrazione con sistemi di supervisione

This driver has been tested on INIM PREVIDIA Ultra, Max and Compact panels.

IO Server Inim Previdia.png

Communication

INIM PREVIDIA panels can be connected via ethernet. A valid IP address must be assigned to the panel. MODBUS PROTOCOL must be enabled. Please refer to the manual for detailed instruction about MODBUS protocol configuration.

HSYCO Configuration

Add a INIMPREVIDIA I/O Server in the I/O Servers section of the Settings and set its parameters:

Communication

  • Address: IP address of the INIM PREVIDIA panel
  • Port: TCP/IP port for MODBUS communication (default 502)

High Availability

  • Shutdown when inactive: defaults to false.

Options

ID Default Values Description
gui true true enable support for the UI object, UISET actions and USER commands
false disable UI support
startupevents false true generate IO events also during the driver’s start-up phase
false start generating events only after HSYCO is aligned with the current status of the system
unitid 1 > 0 MODBUS unit ID of the INIM PREVIDIA panel
pollingtime 1000 n >= 1000, n <= 30000 the data polling interval, in milliseconds.
loopsnumber 16 n = 1..16 the number of configured loops