Mitsubishi
The MITSUBISHI air-conditioning system equipped with one of the centralized controllers among G-50, GB-50, or AG-150 allows for remote control and supervision, via Ethernet communication, of the whole framework.
Contents
Communication
The Mitsubishi controller replies on the port 80 (10 sockets) or 1025 (4 sockets) of its IP address.
M-NET Configuration
This I/O Server complies with the XML API for the Mitsubishi M-NET proprietary protocol.
All the devices comprising the M-NET architecture are assigned an address ranging from 0 to 250.
Conditioners and lossnay modules can be associated to 50 different groups (indexed from 1 to 50). The control of these modules is thus performed addressing the group they belong to.
Further, it is possible to expand the system using up to three ECs which allow to replicate a full M-NET architecture under each EC. In this case, modules are addressed specifying both the EC and the group they belong to.
HSYCO Configuration
Options
ID | Default | Values | Description |
---|---|---|---|
gui | true | true | enable support for the UI object, UISET actions and USER commands |
false | disable UI support | ||
startupevents | false | true | generate IO events also during the driver’s start-up phase |
false | start generating events only after HSYCO is aligned with the current status of the system | ||
pollinterval | 20 | n > 0 | the data acquisition interval, in seconds |
ec | 0 | 0 - 3 | specifies the number of ECs connected to the main controller. A value of 0 indicates that no EC is used |
Datapoints
In the following table replace <target> with system to address the whole framework. If ECs are used you can specify ecS as target to address a single sub-system and as before, it is necessary to prepend the target EC number before specifying the group or the address.
ID | Value | R/W | Description |
---|---|---|---|
connection | online | R | connection established |
offline | R | HSYCO can't connect to the panel | |
<target>.power | 1 | R | at least one group is on |
W | turn all the groups on | ||
0 | R | the whole system is off | |
W | turn the whole system off | ||
<target>.mode | cool dry fan heat auto |
W | set the mode of all the groups to the specified value (Air conditioner modes) |
heatrecovery lcauto bypass |
W | set the mode of all the groups to the specified value (LOSSNAY modes) | |
<target>.temp | 17 - 30 | W | set the temperature of all the groups to the specified value (if compliant with the previously mentioned ranges) |
<target>.airdirection | horizontal mid1 mid2 vertical swing |
W | set the air direction of all the groups to the specified value |
<target>.fanspeed | high mid1 mid2 low |
W | set the speed of the fan of all the groups to the specified value |
<target>.ventilation | high low off |
W | set the operation status of the interlocked LOSSNAY or OA processing unit present in the whole system to the specified value |
<target>.prohibit.drive | 1 | W | prohibit power switching by remote control to all the groups |
0 | W | allow power switching by remote control to all the groups | |
<target>.prohibit.mode | 1 | W | prohibit mode setting by remote control to all the groups |
0 | W | allow mode setting by remote control to all the groups | |
<target>.prohibit.settemp | 1 | W | prohibit temperature setting by remote control to all the groups |
0 | W | allow temperature setting by remote control to all the groups | |
<target>.prohibit.filter | 1 | W | prohibit filter signal reset by remote control to all the groups |
0 | W | allow filter signal reset by remote control to all the groups | |
<target>.reset | error | W | reset the error signal of all the groups |
filter | W | reset the filter signal of all the groups | |
g<n>.power | 1 | R | this group is on |
W | turn this group on | ||
0 | R | this group is off | |
W | turn this group off | ||
g<n>.mode | cool dry fan heat auto |
R | the mode of this group is set to the reported value (Air conditioner modes) |
W | set the mode of this group to the specified value (Air conditioner modes) | ||
autoheat autocool |
R | the mode of this group is set to the reported value (Air conditioner modes) | |
heatrecovery lcauto bypass |
R | the mode of this group is set to the reported value (LOSSNAY modes) | |
W | set the mode of this group to the specified value (LOSSNAY modes) | ||
g<n>.temp | 17 - 30 | R | the set temperature for this group correspond to the reported value (in °C) |
W | set the temperature of this group to the specified value (if compliant with the previously mentioned ranges) | ||
g<n>.inlettemp | 0 - 999 | R | the inlet measured temperature for this group (in tenth of °C) |
g<n>.airdirection | horizontal mid1 mid2 vertical swing |
R | the air direction for this group is set to the reported value |
W | set the air direction of this group to the specified value | ||
g<n>.fanspeed | high mid1 mid2 low |
R | the fan speed for this group is set to the reported value |
W | set the speed of the fan of this group to the specified value | ||
g<n>.ventilation | high low off |
R | the operation status of the interlocked LOSSNAY or OA processing unit present in this group is set to the reported value |
W | set the operation status of the interlocked LOSSNAY or OA processing unit present in this group to the specified value | ||
g<n>.prohibit.drive | 1 | R | the power switching by remote control is prohibited to this group |
W | prohibit power switching by remote control to this group | ||
0 | R | the power switching by remote control is allowed to this group | |
W | allow power switching by remote control to this group | ||
g<n>.prohibit.mode | 1 | R | the mode setting by remote control is prohibited to this group |
W | prohibit mode setting by remote control to this group | ||
0 | R | the mode setting by remote control is allowed to this group | |
W | allow mode setting by remote control to this group | ||
g<n>.prohibit.settemp | 1 | R | the temperature setting by remote control is prohibited to this group |
W | prohibit temperature setting by remote control to this group | ||
0 | R | the temperature setting by remote control is allowed to this group | |
W | allow temperature setting by remote control to this group | ||
g<n>.prohibit.filter | 1 | R | the filter signal reset by remote control is prohibited to this group |
W | prohibit filter signal reset by remote control to this group | ||
0 | R | the filter signal reset by remote control is allowed to this group | |
W | allow filter signal reset by remote control to this group | ||
g<n>.filter | 1 | R | the filter signal of this group is on |
0 | R | the filter signal of this group is off | |
g<n>.error | 1 | R | the error signal of this group is on |
0 | R | the error signal of this group is off | |
g<n>.reset | filter | W | reset the filter signal of this group |
error | W | reset the error signal of this group | |
a<m>.error | 0 | R | no error is reported for this address |
<xxxx> | R | the error with code <xxxx> is reported for this address | |
system.error | 1 | R | an error is detected on some address |
0 | R | no error detected on any address |
User Interface
In the following tables, replace <n> with a group number ranging from 1 to 50, and replace <m> with an address from 0 to 250. If one or more ECs are used (i.e. the option field “ec” is set to a value greater than 0), it is necessary to specify the EC number we are addressing. To this end, prepend the string “ecS.” (with S ranging from 1 to the specified value of ECs) to the target group or the address.
For instance, when an EC is used the following ID or name is not correct:
mits.g1.power
The correct one to be used is the following:
mits.ec1.g1.power