The Wyrestorm MX0606-PP, MX0606-PP, and MX0606-PP modules are matrix switchers that allow any of their HDMI inputs to be routed over distance to any combination of their display outputs via a single UTP cable. The integration with HSYCO can be accomplished via direct control through the RS-232 port on the module.
Communication
Use a DE-9 (often called DB-9) female-male RS-232 straight cable to connect the RS-232 port on the Wyrestorm module to the serial port on HSYCO server.
RS-232 parameters:
Baud rate | 9600 |
Data bits | 8 |
Stop bit | 1 |
Parity | none |
Flow control | none |
HSYCO Configuration
Options
ID | Default | Values | Description |
---|---|---|---|
gui | true | true | enable support for the UI object, UISET actions and USER commands |
false | disable UI support | ||
startupevents | false | true | generate IO events also during the driver’s start-up phase |
false | start generating events only after HSYCO is aligned with the current status of the system | ||
outputs | 4 | 4 | 6 | 8 | number of outputs on the module |
wyrestorm.ini
The wyrestorm.ini file is an optional configuration file located in the root directory.
Here you can define the names to assign to the inputs so that they will be automatically added in the objects of the UI interface. Add a new line for each name using the format “<ioserver_id>.in.<n> = <name>”, where <ioserver_id> is the ID of the referred I/O server and <n> is the input number.
For instance:
wyr.in.1 = TV wyr.in.2 = DVD wyr.in.5 = PC