ESC/VP
This I/O Server control SEIKO EPSON projectors which include a wide range of multi-source projectors remotely controllable via Ethernet, serial port, and USB connection. HSYCO SERVER integrates these devices through Ethernet connection.
The used protocol is compliant with the ESC/VP21 protocol specifications.
Contents
Projector Configuration
In order to be able to control the device with HSYCO some initial configuration of the SEIKO EPSON device is needed.
In the “Network” section of the main menu, assign a suitable fixed IP address to the device and set the DHCP option to off.
Further, in the “Extended” section, make sure the option “Standby mode” is set to “communication on”.
HSYCO Configuration
Options
ID | Default | Values | Description |
---|---|---|---|
gui | true | true | enable support for UISET actions and USER commands |
false | disable UI support | ||
pollinterval | 3 | n > 0 | the data acquisition interval, in seconds |
Datapoints
ID | Value | R/W | Description |
---|---|---|---|
connection | online | R | connection established |
offline | R | HSYCO can't connect to the device | |
power | 1 | R | the projector is on and ready |
W | turn on the projector | ||
0 | R | the projector is off or not ready | |
W | turn off the projector | ||
status | on | R | the projector is on and ready |
off | the projector is off | ||
warming | the projector is warming up | ||
cooling | the projector is cooling down | ||
error | the projector is in a standby error state | ||
lamp | 0 ... 65535 | R | the lamp hours |
luminance | low | R | the luminance is set to low |
W | set luminance to low | ||
high | R | the luminance is set to high | |
W | set luminance to high | ||
mute | 1 | R | the A/V mute is on |
W | set A/V mute to on | ||
0 | R | the A/V mute is off | |
W | set A/V mute to off | ||
msel | black | R | the mute screen is set to black |
W | set the mute screen to black | ||
blue | R | the mute screen is set to blue | |
W | set the mute screen to blue | ||
logo | R | the mute screen is set to show the user logo | |
W | set the mute screen to show the user logo | ||
source | <src> | R | the current source is <src> |
W | set the source to <src> | ||
command | <cmd> | W | send <cmd> as command to the projector. The command must be compliant with the ESC/VP21 protocol |
User Interface
UISET Actions
ID | Attribute | Set to | |
---|---|---|---|
connection | visible | true | when datapoint connection = offline |
false | when datapoint connection = online | ||
power | value | ON | when the projector is on and ready |
OFF | when the projector is off or not ready | ||
lamp | value | number of hours of activity of the lamp. | |
visible | true | when the projector is on | |
false | when the projector is off | ||
luminance | value | HIGH | when the luminance is set to high |
LOW | when the luminance is set to low | ||
visible | true | when the projector is on | |
false | when the projector is off | ||
mute | value | ON | when the A/V mute function is on |
OFF | when the A/V mute function is off | ||
msel | value | BLACK | when the mute screen is set to black |
BLUE | when the mute screen is set to blue | ||
LOGO | when the mute screen is set to show the user logo |
USER Commands