Events Programming
The EVENTS programming environment is based on a simple language that associates one or more actions to a field event or combination of conditions.
Programming EVENTS is as simple as editing the events.txt file, located in the main directory. Compared to Java, there is no compilation process. When you save the file, it is automatically reloaded and becomes immediately effective.
An event is an expression that refers to the persistent status or transient event of devices, to conditions applied to local variables, and to various internal events. An action is a control command sent to a device, or several other internal functions, like setting variables and program timers.
Example:
IO k.33 = 1 : k.34 = 1
when the light actuator with data point name k.33 is turned on, HSYCO automatically turns on the actuator with data point name k.34.
Example:
DAY : IO k.33 k.34 k.35 k.36 = 0
at sunrise, the actuators named k.33, k.34, k.35 and k.36 are turned off.
In this chapter we will describe the general format of events.txt, and all the built-in events and actions.
The events.txt file is usually modified with the text editor in HSYCO’s File Manager. When you save the file, it is automatically checked and, if errors are found, a warning icon appears in the top bar.
Touch that icon to show the list of errors. Errors are also written in the log file. Lines containing errors are ignored.
You can also enable the editor’s syntax highlighter for improved readability.
The EVENTS Language
EVENTS uses the simple format:
event : actions
Several events can be combined together to implement complex expressions which represent the combination of different conditions.
The logical operators AND, OR, NOT and the round brackets are available to define the operations precedence.
If the brackets are not used, the AND and OR operations are executed from left to right. The NOT operator has priority and is executed on the first expression after it, before AND or OR conditions.
Example:
IO k.33 OR IO K.34
this event occurs any time the actuators 33 or 34 change their status.
Example:
CAMERA "entrance" AND NOT IO K.34 = 0
is an event that occurs when the camera “entrance” starts recording, but only if the K.34 datapoint is not 0.
Example:
IO k.33 > 5 OR IO K.34 = 0 AND IO K.35 = 0
is equivalent to
(IO k.33 > 5 OR IO K.34 = 0) AND IO K.35 = 0
Example:
NOT IO k.33 = 1 AND IO k.34 = 1
is equivalent to
(NOT IO k.33 = 1) AND IO k.34 = 1
Comments
Comments are vital to describe the functions, even if the EVENTS language is very easy to understand.
A comment is identified by the # character.
All characters following # will be ignored until the end of line, unless the # character is enclosed between double quotes.
Example:
# actions executed at sunset NIGHT: <tab>IO k.33 k.34 k.35 k.36 = 1, # garden lights on IO k.43 k.44 = UP, # rise the awnings LOG = "# and this is not a comment"