An event is defined as a keyword that identifies the event type, usually followed by one or more parameters and conditional operators. Every keyword uses a specific syntax that interprets parameters according to its own rules.


System Events

DAY

HAACTIVE

HSYCOSTART

NIGHT

POWER

PROGRAMTIMER

SUNAZIMUTH

SUNELEVATION

TIME

Cameras

CAMERA

CAMERACOMMAND

CAMERAVIEW

DMX

DMX

Events on the DMX bus channels.


Event State Description
DMX address transient any change to the channel value
DMX address = ON stable channel value > 0
DMX address = OFF stable channel value = 0
DMX address = value

DMX address > value DMX address < value DMX address >= value DMX address <= value

stable the channel value is equal, greater, greater or equal, less, less or equal to the given value.

Valid values are numbers between 0 and 255


Parameters:

  • address - when using one DMX gateway, address will be a standard DMX-512 address between 1 and 512. If there is more than one gateway, 1000 must be added to the DMX address for the second gateway, 2000 for the third one and so on. For example, 2100 stands for the address 100 on the DMX bus controlled by the third gateway.


Examples:

DMX 100 = ON
DMX 1200 = OFF
DMX 135 = OFF OR DMX 100 > 50
DMX 41 <= $LEVEL

DMXSTART

This event is triggered when starting the monitor threads for each DMX bus, once per bus at the start of the execution of HSYCO, and also after every restart of the monitor thread.


Event State Description
DMXSTART busid transient occurs when HSYCO connects to the DMX gateway.

HSYCO establishes the connection at start-up.

If the gateway is turned off and then on, or if communication errors occur, HSYCO automatically re-establishes the connection as soon as possible, calling this event in case of success.


Parameters:

  • busid - the id of the DMX gateway. The first gateway has address 0. The second has address 1, etc. busid can be omitted if 0.

Examples:

DMXSTART: DMX 100-200 = OFF
DMXSTART 1: DMX 1100-1200 = OFF

Infrared Control

IR

I/O Servers

IO

Triggered by a status change of any data port of an I/O server.


Event State Description
IO name transient any change of an I/O variable
IO name = value

IO name > value
IO name < value
IO name >= value
IO name <= value

stable the value is equal, greater, greater or equal, less, less or equal to the given value.

Note The names and values of the I/O variables are specifically related to the type of I/O server. Values can be numeric or strings.


Parameters:

  • name - the data point name of the input or output port. According to the type of server, the format changes but it generally appears as server name, as declared with the ioServers parameter in hsyco.ini, followed by a dot and the input/output port name. See the Application Notes for more information.


Examples:

IO tempmeter.indoor > 25.5
IO contacts.c1 = 1

IOSTART

This event indicates that the connection with an I/O server has been correctly established.

It should be safe to associate this event with actions that set the I/O server writable variables.


Event State Description
IOSTART id transient Triggered by the start of the communication thread of each I/O server - once for each server at the beginning of the execution of HSYCO, and also after every reboot of the communication thread, for example after communication errors.


Parameters:

  • id - the I/O server number, starting from 0, based on the listing order of the ioServers parameter in hsyco.ini; If only one I/O server is available, it can be omitted.


Examples:

IOSTART: IO contacts.c1 = 1
IOSTART 2: IO relays.door = 1

Leak Detector

LEAK

Network Services

LOCATION

PING

URL

PBX

PBX

Squeezebox

MUSIC

Timers and Schedulers

TIMER

User Interface

PAGE

USER