Guardall
Guardall QX32i, PX80 and PX500 are multi-area security systems. The integration with HSYCO can be accomplished via direct control through the RS-232 port on the panel. Th I/O Server supports QX32i, PX80 and PX500 Guardall units with software version 4.33.
Communication
Employ a female-female RS-232 crossed cable to connect the panel directly to HSYCO or to an Ethernet/RS-232 gateway. The cable must follow this pinout diagram:
2 ↔ 3 3 ↔ 2 5 ↔ 5 7 ↔ 8 8 ↔ 7
RS-232 parameters:
Baud rate | 9600 |
Data bits | 8 |
Stop bit | 1 |
Parity | none |
Flow control | none |
Guardall Configuration
You must configure the unit to enable serial communication even if the system is armed. Digit the technician code on the keypad and select menu entry "99" (Total Configuration), then select entry “10” (Communication) and make sure that the serial connection is enabled when the system is armed (on).
Moreover, it is necessary to enable the required features to be available remotely. To this end, from the technician’s menu, select again menu entry “99”, then “12”. Here enter the number 1 and modify the settings accordingly to your requirements.
HSYCO Configuration
Options
ID | Default | Values | Description | ||
---|---|---|---|---|---|
gui | true | true | enable support for the UI object, UISET actions and USER commands | ||
false | disable UI support | ||||
startupevents | false | true | generate IO events also during the driver’s start-up phase | ||
false | start generating events only after HSYCO is aligned with the current status of the system | ||||
logsize | 20 | n ≥ 0 | the number of log lines to display in the UI object | ||
arm | true | true | allow groups arming | ||
false | deny groups arming | disarm | true | true | allow groups disarming |
false | deny groups disarming |