Giacomini
The Giacoklima bus system equipped with the KM203 network controller allows for remote control and supervision, via Serial communication, of the whole heating/cooling framework.
Contents
Communication
Connect HSYCO to the KM203 controller employing an RS485 gateway.
RS-232 parameters:
Baud rate | 19200 |
Data bits | 8 |
Stop bit | 1 |
Parity | none |
Flow control | none |
The Giacoklima bus architecture
This image illustrates an example of the system architecture:
The RS-485 port is on the top left corner of the KM203 interface as shown in the picture above.
HSYCO Configuration
Options
ID | Default | Values | Description |
---|---|---|---|
gui | true | true | enable support for the UI object, UISET actions and USER commands |
false | disable UI support | ||
startupevents | false | true | generate IO events also during the driver’s start-up phase |
false | start generating events only after HSYCO is aligned with the current status of the system | ||
pollinterval | 1 | n > 0 | the data acquisition interval, in seconds |
The Giacoklima bus architecture
The gkbus.ini file is a specific configuration file located in the main directory (same directory as hsyco.ini or hsyco.jar).
Here you must add a line for each thermostat belonging to the framework and optionally specify a descriptive name of the corresponding area.
Use the format “<ioserver_id>.k<n>.<addr> = name”, where <ioserver_id> is the id of the referred I/O server, <n> is the number of the KPM20 module the thermostat is connected to and <addr> is the secondary address of the thermostat.
For instance:
gk.k0.0 = Kitchen gk.k0.1 = Bedroom gk.k1.0 = Entrance
Datapoints
ID | Value | R/W | Description |
---|---|---|---|
connection | online | R | connection established |
offline | R | HSYCO can’t connect to the panel | |
k<n>.<addr>.name | <name> | R | the name of the addressed thermostat is set to the reported string |
k<n>.<addr>.temp | <val> | R | the room temperature measured by the addressed thermostat is equal to <val> in °C/10 |
k<n>.<addr>.setpoint.temp | <val> | R | the set-point temperature measured by the addressed thermostat is equal to <val> in °C/10 |
W | set the set-point temperature of the addressed thermostat to <val> in °C/10 | ||
k<n>.<addr>.humidity | <val> | R | the relative humidity measured by the addressed thermostat is equal to <val> |
season | summer | R | the current season is set to summer |
W | set the current season to summer | ||
winter | R | the current season is set to winter | |
W | set the current season to winter | ||
k<n>.<addr>.mode | off | R | the addressed thermostat is set to mode “OFF” |
W | set the addressed thermostat to mode “OFF” | ||
com | R | the addressed thermostat is set to mode “Comfort” | |
W | set the addressed thermostat to mode “Comfort” | ||
stb | R | the addressed thermostat is set to mode “Stand-by” | |
W | set the addressed thermostat to mode “Stand-by” | ||
ngt | R | the addressed thermostat is set to mode “Night" | |
W | set the addressed thermostat to mode “Night” | ||
mode | off | W | set all the thermostats to mode “OFF” |
com | W | set all the thermostats to mode “Comfort” | |
stb | W | set all the thermostats to mode “Stand-by” | |
ngt | W | set all the thermostats to mode “Night” | |
k<n>.pump | 0 | R | the pump of the addressed KPM20 module is not active |
1 | R | the pump of the addressed KPM20 module is active | |
k<n>.in.temp | <val> | R | the inlet temperature of the addressed KPM20 module is equal to <val> |
k<n>.out.temp | <val> | R | the return temperature of the addressed KPM20 module is equal to <val> in °C/10 |
k<n>.setpoint.temp | <val> | R | the working set-point temperature of the addressed KPM20 module is equal to <val> in °C/10 |
k<n>.valve | <val> | R | the opening percentage value of the mixing valve calculated by the addressed KPM20 module is equal to val |
ext.temp | <val> | R | the measured external temperature is equal to <val> in °C/10 |
t1.winter | <val> | R | the T1 temperature parameter’s value for winter climatic compensation is equal to <val> in °C/10 |
W | set the T1 temperature parameter’s value for winter climatic compensation to <val> in °C/10 | ||
t2.winter | <val> | R | the T2 temperature parameter’s value for winter climatic compensation is equal to <val> in °C/10 |
W | set the T2 temperature parameter’s value for winter climatic compensation to <val> in °C/10 | ||
lim.winter | <val> | R | the T-Lim temperature parameter’s value for winter climatic compensation is equal to <val> in °C/10 |
W | set the T-Lim temperature parameter’s value for winter climatic compensation to <val> in °C/10 | ||
setpoint.winter | <val> | R | the minimum set-point temperature for winter is equal to <val> in °C/10 |
W | set the minimum set-point temperature for winter to <val> in °C/10 | ||
setpoint.summer | <val> | R | the minimum set-point temperature for summer is equal to <val> in °C/10 |
W | set the minimum set-point temperature for summer to <val> in °C/10 |
User Interface
You can use a tempmini object to create a thermostat-equivalent interface.
Set the Server ID field to the I/O Server’s name and specify the address of the thermostat (K483 module) in the Address field using the format “k<n>.<addr>” where <n> is the number of the KPM20 module the thermostat is connected to and <addr> is its address (e.g. k0.1 represents the second thermostat connected to the first KPM20):
UISET Actions
ID | Attribute | Set to | |
---|---|---|---|
k<n>.<addr>.name | value | shows the name assigned to the addressed thermostat | |
k<n>.<addr>.temp | value | shows the measured room temperature in °C by the addressed thermostat | |
k<n>.<addr>.setpoint.temp | value | shows the set-point temperature in °C on the addressed thermostat | |
k<n>.<addr>.humidity | value | shows the measured relative humidity by the addressed thermostat | |
k<n>.in.temp | value | shows the inlet temperature of the addressed KPM20 module | |
k<n>.out.temp | value | shows the return temperature of the addressed KPM20 module | |
k<n>.setpoint.temp | value | shows the working set-point temperature in °C on the addressed KPM20 module | |
k<n>.valve | value | shows the opening percentage value of the mixing valve calculated by the addressed KPM20 module | |
ext.temp | value | shows the measured external temperature in °C | |
t1.winter | value | shows the T1 temperature parameter’s value for winter climatic compensation in °C | |
t2.winter | value | shows the T2 temperature parameter’s value for winter climatic compensation in °C | |
lim.winter | value | shows the T-Lim temperature parameter’s value for winter climatic compensation in °C | |
setpoint.winter | value | shows the minimum set-point temperature for winter | |
setpoint.summer | value | shows the minimum set-point temperature for summer | |
connection.label.online | visible | true when the system is connected to HSYCO, false otherwise | |
connection.label.offline | visible | true when the system is not connected to HSYCO, false otherwise | |
season.label.winter | visible | true when the current season is set to winter, false otherwise | |
season.label.summer | visible | true when the current season is set to summer, false otherwise | |
k<n>.<addr>.mode.label.off | visible | true when the addressed thermostat is OFF, false otherwise | |
k<n>.<addr>.mode.label.com | visible | true when the working mode of the addressed thermostat is set to “comfort”, false otherwise | |
k<n>.<addr>.mode.label.stb | visible | true when the working mode of the addressed thermostat is set to “stand-by”, false otherwise | |
k<n>.<addr>.mode.label.ngt | visible | true when the working mode of the addressed thermostat is set to “night”, false otherwise | |
k<n>.<addr>.relay.label.0 | visible | true when the relay of the addressed thermostat is not active, false otherwise | |
k<n>.<addr>.relay.label.1 | visible | true when the relay of the addressed thermostat is active, false otherwise | |
k<n>.pump.label.0 | visible | true when the pump of the addressed KPM20 module is not active, false otherwise | |
k<n>.pump.label.1 | visible | true when the pump of the addressed KPM20 module is active, false otherwise |
USER Commands
Name | Param | Action |
---|---|---|
k<n>.<addr>.setpoint.temp | <val> | sets the set-point temperature of the addressed thermostat to the specified value (expressed in °C/10) |
up | increases the set-point temperature of the addressed thermostat by 0.5°C | |
down | decreases the set-point temperature of the addressed thermostat by 0.5°C | |
k<n>.<addr>.mode | off | sets the addressed thermostat on mode “OFF” |
com | sets the addressed thermostat on mode “Comfort” | |
stb | sets the addressed thermostat on mode “Stand-by” | |
ngt | sets the addressed thermostat on mode “Night” | |
season | summer | sets the working mode season to summer |
winter | sets the working mode season to winter | |
t1.winter | <val> | sets the T1 temperature parameter’s value for winter climatic compensation to the specified value (in °C/10) |
t2.winter | val | sets the T2 temperature parameter’s value for winter climatic compensation to the specified value (in °C/10) |
lim.winter | <val> | sets the T-Lim temperature parameter’s value for winter climatic compensation to the specified value (in °C/10) |
setpoint.winter | <val> | sets the minimum set-point temperature for winter to the specified value (in °C/10) |
setpoint.summer | <val> | sets the minimum set-point temperature for summer to the specified value (in °C/10) |
Release Notes
3.3.0
- initial version release
Giacomini, GKBus and Giacoklima are registered trademarks of Giacomini SpA.