Notifier

From HSYCO
Jump to navigation Jump to search

The NOTIFIER AM-2000, AM-4000 and AM-6000 are multi-area fire panels. The integration with HSYCO can be accomplished via a standard Modbus RTU slave interface.

IO Server Notifier Panel.png

Communication

The NOTIFIER SIB 600 Modbus interface is required. The default connection parameters are:

Modbus address: 1 (can be set to 1-32)

RS-485 parameters:

Baud rate 9600
Data bits 8
Stop bit 1
Parity none
Flow control none

Refer to the Notifier manuals for installation, wiring and power supply requirements.

HSYCO Configuration

Options

ID Default Values Description
address 1 1 ... 32 the panel’s Modbus address
gui true true enable support for the UI object, UISET actions and USER commands
false disable UI support
startupevents false true generate IO events also during the driver’s start-up phase
false start generating events only after HSYCO is aligned with the current status of the system
pollinterval 1 > 0 set to the highest zone number configured in the panel. Set to 0 to disable zone status polling and control commands
lastzone 150 0 ... 150 set to the highest zone number configured in the panel. Set to 0 to disable zone status polling and control commands
loglines 100 ≥ 0 if GUI support is enabled, set to the maximum number of lines to show in the log text object. Set to 0 to disable the GUI log

Datapoints

ID Value R/W Description


User Interface

UISET Actions

You can use any object that accepts a text attribute, usually text, but also marquee and others, to display the status of the system according to the following table:

USER Commands

You can use the user object, or any other GUI object that generates user events, to execute any command that could be sent writing to a data point, as defined in the | Datapoints table. Set the user object’s name field to the datapoint (event) name, prefixed by the IO Server id, and its param field to the value that should be written to execute the command.

For example, to disable zone 1, use the following object:

(user fire.zone.1.disabled; 1; r4c2; gr; zone 1 off)

To enable zone 1:

(user fire.zone.1.disabled; 0; r4c3; gr; zone 1 on)

Release Notes

3.3.0

  • initial release


Honeywell and Notifier are registered trademarks owned by Honeywell International Inc., or its subsidiaries or affiliates.

ID Attribute Set to