Notifier
The NOTIFIER AM-2000, AM-4000 and AM-6000 are multi-area fire panels. The integration with HSYCO can be accomplished via a standard Modbus RTU slave interface.
Contents
Communication
The NOTIFIER SIB 600 Modbus interface is required. The default connection parameters are:
Modbus address: 1 (can be set to 1-32)
RS-485 parameters:
Baud rate | 9600 |
Data bits | 8 |
Stop bit | 1 |
Parity | none |
Flow control | none |
Refer to the Notifier manuals for installation, wiring and power supply requirements.
HSYCO Configuration
Options
ID | Default | Values | Description |
---|---|---|---|
address | 1 | 1 ... 32 | the panel’s Modbus address |
gui | true | true | enable support for the UI object, UISET actions and USER commands |
false | disable UI support | ||
startupevents | false | true | generate IO events also during the driver’s start-up phase |
false | start generating events only after HSYCO is aligned with the current status of the system | ||
pollinterval | 1 | > 0 | set to the highest zone number configured in the panel. Set to 0 to disable zone status polling and control commands |
lastzone | 150 | 0 ... 150 | set to the highest zone number configured in the panel. Set to 0 to disable zone status polling and control commands |
loglines | 100 | ≥ 0 | if GUI support is enabled, set to the maximum number of lines to show in the log text object. Set to 0 to disable the GUI log |
Datapoints
ID | Value | R/W | Description |
---|---|---|---|
connection | online | R | connection established |
offline | R | HSYCO can't connect to the panel | |
annunciator.<n>.<m>.offline | 1 | R | annunciator <n>.<m> offline |
0 | R | annunciator <n>.<m> online | |
annunciator.<n>.<m>.fault | 1 | R | annunciator <n>.<m>fault |
0 | R | annunciator <n>.<m> no fault | |
annunciator.<n>.<m>.cfg.error | 1 | R | annunciator <n>.<m> configuration error |
0 | R | annunciator <n>.<m> configured | |
lcd.<n>.offline | 1 | R | LCD <n> offline |
0 | R | LCD <n> online | |
lcd.<n>.fault | 1 | R | LCD <n> fault |
0 | R | LCD <n> no fault | |
lcd.<n>.cfg.error | 1 | R | LCD <n> configuration error |
0 | R | LCD <n> configured | |
loop.<n>.short | 1 | R | loop <n> short circuit |
0 | R | loop <n> no short circuit | |
loop.<n>.open | 1 | R | loop <n> open fault |
0 | R | loop <n> no open fault | |
loop.<n>.voltage | 1 | R | loop <n> low voltage fault |
0 | R | loop <n> no low voltage fault | |
module.<l>.<n>.normal | 1 | R | module <n> on loop <l> normal state |
0 | R | module <n> on loop <l> error state | |
module.<l>.<n>.disabled | 1 | R | module <n> on loop <l> disabled |
W | disable module <n> on loop <l> | ||
0 | R | module <n> on loop <l> enabled | |
W | enable module <n> on loop <l> | ||
module.<l>.<n>.disabled | 1 | R | module <n> on loop <l> output active (ON) |
W | turn ON out of module <n> on loop <l> | ||
0 | R | module <n> on loop <l> output not active (OFF) | |
W | turn OFF out of module <n> on loop <l> | ||
module.<l>.<n>.fault | 1 | R | module <n> on loop <l> fault |
0 | R | module <n> on loop <l> no fault | |
module.<l>.<n>.alarm | 1 | R | module <n> on loop <l> alarm |
0 | R | module <n> on loop <l> no alarm | |
panel.fault.batt.disconn | 1 | R | batteries disconnected |
0 | R | batteries connected | |
panel.fault.power | 1 | R | batteries disconnected |
0 | R | batteries connected | |
panel.fault.batt.unbal | 1 | R | batteries disconnected |
0 | R | batteries connected | |
panel.fault.batt.fail | 1 | R | batteries unbalanced charge |
0 | R | batteries no unbalanced charge | |
panel.fault.bex | 1 | R | external batteries fault |
0 | R | no external batteries fault | |
panel.fault.earth | 1 | R | ground connection fault |
0 | R | no ground connection fault | |
panel.fault.undervoltage | 1 | R | AC power under-voltage fault |
0 | R | no AC power under-voltage fault | |
panel.fault.overvoltage | 1 | R | AC power over-voltage fault |
0 | R | no AC power over-voltage fault | |
panel.fault.loop.open | 1 | R | at least one loop is open |
0 | R | no loops open | |
panel.fault.loop.short | 1 | R | at least one loop short circuit |
0 | R | no loop short circuit | |
panel.fault.fuse.user | 1 | R | fuse fault |
0 | R | fuse ok | |
panel.fault.batt.charger.undervoltage | 1 | R | battery charger under-voltage fault |
0 | R | no battery charger under-voltage fault | |
panel.fault.batt.charger.overvoltage | 1 | R | battery charger over-voltage fault |
0 | R | no battery charger over-voltage fault | |
panel.filesystem.clear.error | 1 | R | memory delete error |
0 | R | no memory delete error | |
panel.filesystem.init.error | 1 | R | memory initialization error |
0 | R | no memory initialization error | |
panel.reliab.par.mod | 1 | R | reliability parameters modified warning |
0 | R | no reliability parameters modified warning | |
panel.hardkey.enabled | 1 | R | hardware programming key enabled |
0 | R | hardware programming key not enabled | |
panel.power.on | 1 | R | power on phase |
0 | R | power on phase completed | |
panel.wdt.reset | 1 | R | main CPU watchdog fault |
0 | R | main CPU watchdog ok | |
panel.cfg.error | 1 | R | configuration error |
0 | R | configuration ok | |
panel.filesystem.error | 1 | R | memory corruption |
0 | R | memory ok | |
panel.hard.clock | 1 | R | internal hardware clock fault |
0 | R | internal hardware clock ok | |
panel.arch.full | 1 | R | log archive full |
0 | R | log archive not full | |
panel.arch.full.warning | 1 | R | log archive warning (80% full) |
0 | R | no log archive warning | |
panel.zone.default | 1 | R | sensors not yet assigned to zones |
0 | R | zones assignment done | |
panel.sib.offline | 1 | R | SIB board offline |
0 | R | SIB board online | |
panel.sib.not.prg | 1 | R | SIB board not programmed |
0 | R | SIB board programmed | |
panel.pc.invalid.cmd | 1 | R | invalid command from PC |
0 | R | no invalid command from PC | |
panel.arch.disabled | 1 | R | log archive disabled |
0 | R | log archive disabled | |
panel.lib.<n>.offline | 1 | R | LIB board <n> offline |
0 | R | LIB board <n> online | |
panel.lib.<n>.cfg.error | 1 | R | LIB board <n> configuration error |
0 | R | LIB board <n> configured | |
panel.lib.<n>.not.prg | 1 | R | LIB board <n> not programmed |
0 | R | LIB board <n> programmed | |
panel.fire | silence | W | fire alarm silence |
reset | R | fire alarm reset | |
panel.fire.normal | 1 | R | fire panel normal state |
0 | R | fire panel error state | |
panel.fire.exclusions | 1 | R | fire panel has one or more disabled components |
0 | R | fire panel’s all components are enabled | |
panel.fire.test | 1 | R | fire panel test |
0 | R | fire panel no test | |
panel.fire.fault | 1 | R | fire panel fault |
0 | R | fire panel no fault | |
panel.fire.alarm | 1 | R | fire panel alarm |
0 | R | fire panel no alarm | |
panel.fire.alarm.silent | 1 | R | fire panel alarm silenced |
0 | R | fire panel no alarm silenced | |
panel.fire.unknown | 1 | R | fire panel unknown events |
0 | R | fire panel no unknown events | |
panel.tech | silence | R | technical alarm silence |
reset | R | technical alarm reset | |
panel.tech.normal | 1 | R | technical panel normal state |
0 | R | technical panel error state | |
panel.tech.exclusions | 1 | R | technical panel has one or more disabled components |
0 | R | technical panel’s all components are enabled | |
panel.tech.test | 1 | R | technical panel test |
0 | R | technical panel no test | |
panel.tech.fault | 1 | R | technical panel fault |
0 | R | technical panel no fault | |
panel.tech.alarm | 1 | R | technical panel alarm |
0 | R | technical panel no alarm | |
panel.tech.unknown | 1 | R | technical panel unknown events |
0 | R | technical panel no unknown events | |
sensor.<l>.<n>.normal | 1 | R | sensor <n> on loop <l> normal state |
0 | R | sensor <n> on loop <l> error state | |
sensor.<l>.<n>.disabled | 1 | R | sensor <n> on loop <l> disabled |
W | disable sensor <n> on loop <l> | ||
0 | R | sensor <n> on loop <l> enabled | |
W | enable sensor <n> on loop <l> | ||
sensor.<l>.<n>.prealarm.1 | 1 | R | sensor <n> on loop <l> pre-alarm 1 |
0 | R | sensor <n> on loop <l> pre-alarm 1 off | |
sensor.<l>.<n>.prealarm.2 | 1 | R | sensor <n> on loop <l> pre-alarm 2 |
0 | R | sensor <n> on loop <l> pre-alarm 2 off | |
sensor.<l>.<n>.fault | 1 | R | sensor <n> on loop <l> fault |
0 | R | sensor <n> on loop <l> no fault | |
sensor.<l>.<n>.alarm | 1 | R | sensor <n> on loop <l> alarm |
0 | R | sensor <n> on loop <l> no alarm | |
zone.<n>.normal | 1 | R | zone <n> normal state |
0 | R | zone <n> error state | |
zone.<n>.disabled | 1 | R | zone <n> disabled |
W | disable zone <n> | ||
0 | R | zone <n> enabled | |
W | enable zone <n> | ||
zone.<n>.fault | 1 | R | zone <n> fault |
0 | R | zone <n> no fault | |
zone.<n>.alarm | 1 | R | zone <n> alarm |
0 | R | zone <n> no alarm |
User Interface
UISET Actions
You can use any object that accepts a text attribute, usually text, but also marquee and others, to display the status of the system according to the following table:
USER Commands
You can use the user object, or any other GUI object that generates user events, to execute any command that could be sent writing to a data point, as defined in the | Datapoints table. Set the user object’s name field to the datapoint (event) name, prefixed by the IO Server id, and its param field to the value that should be written to execute the command.
For example, to disable zone 1, use the following object:
(user fire.zone.1.disabled; 1; r4c2; gr; zone 1 off)
To enable zone 1:
(user fire.zone.1.disabled; 0; r4c3; gr; zone 1 on)