Airzone

From HSYCO
Revision as of 11:36, 7 January 2014 by Hsyco (talk | contribs) (→‎Options)
Jump to navigation Jump to search

Airzone is a control framework for ducted air conditioning systems which allows for the control of several zones independently. This I/O server provides support for this Airzone systems: INNOBUS, FLEXA, ANTREE and CEN.

Communication

Airzone communicates with HSYCO through a modbus connection employing a RS-485 gateway.

RS-485 parameters:

Baud rate 19200
Data bits 8
Stop bit 1
Parity even
Flow control none

HSYCO Configuration

Options

ID Default Values Description
gui true true enable support for the UI object, UISET actions and USER commands
false disable UI support
startupevents false true generate IO events also during the driver’s start-up phase
false start generating events only after HSYCO is aligned with the current status of the system
pollinterval 20 n > 0 the data acquisition interval, in seconds
version 1 1 use protocol version 1
2 use protocol version 2