Kilsen
KILSEN KFP-A are multi-area fire panels. The integration with HSYCO can be accomplished via a standard Modbus TCP/IP connection. This I/O server was developed following the MODBUS documentation P/N 00-3243-505-1603-01 • ISS 14DEC15
Communication
KILSEN panels can be connected via ethernet. A valid IP address must be assigned to the panel. MODBUS PROTOCOL must be enabled. Please refer to the manual for detailed instruction about MODBUS protocol configuration.
HSYCO Configuration
Add a KILSEN I/O Server in the I/O Servers section of the Settings and set its parameters:
Communication
- Address: IP address of the KILSEN panel
- Port: TCP/IP port for MODBUS communication (default 502)
High Availability
- Shutdown when inactive: defaults to false.
Options
ID | Default | Values | Description |
---|---|---|---|
address | 1 | 1 ... 32 | the panel’s Modbus address |
gui | true | true | enable support for the UI object, UISET actions and USER commands |
false | disable UI support | ||
startupevents | false | true | generate IO events also during the driver’s start-up phase |
false | start generating events only after HSYCO is aligned with the current status of the system | ||
pollinterval | 1 | > 0 | the data acquisition interval, in seconds |
lastzone | 150 | 0 ... 150 | set to the highest zone number configured in the panel. Set to 0 to disable zone status polling and control commands |
loglines | 100 | ≥ 0 | if GUI support is enabled, set to the maximum number of lines to show in the log text object. Set to 0 to disable the GUI log |
protocolversion | 2 | 1 | set this option to 1 only if the panel is using the old firmware |
2 | default protocol support for panels with new firmware (N models) |