Protege

From HSYCO
Revision as of 07:25, 14 August 2019 by Enrico (talk | contribs)
Jump to navigation Jump to search

Protege is a server based architecture enabling you to securely manage, control and monitor a number of users, doors, areas, and other devices. The integration with HSYCO can be accomplished with a TCP/IP network connection.

ProtegeGXServer needs to be configured to accept a connection on a defined TCP/IP port with the ICT Automation and Control Service protocol. A PIN must be set (4 to 6 digits) Disable encryption and checksum Select Little Endian format Enable Login Block after PIN error

HSYCO Configuration

Add a PROTEGE I/O Server in the I/O Servers section of the Settings and set its parameters:

Communication

  • IP Address: the ICT Protege Server panel address
  • IP Port: TCP/IP port enabled on the ICT Protege Server

High Availability

  • Shutdown when inactive: defaults to true.

Options

ID Default Values Description
pin pin the user PIN that the driver uses when sending commands to the Protege system. It must be a valid user code, able to engage and disengage the panel.
startupevents false true generate IO events also during the driver’s start-up phase
false start generating events only after HSYCO is aligned with the current status of the system
gui true true enable support of the tecnoalarm Web interface object
false disable support of the tecnoalarm Web interface object
debug false true generates additional logs that can be viewed in verbose mode
false debug logging disabled
areaslist string list of all the areas that are declared on the panel. Areas could not be consecutive and special characters "-" and ";" are used for intervals definition. E.G. 0-3;5-9 means areas from 0 to 3, from 5 to 9. E.G. 4;15 means area number 4 and number 15
polltime 1000 n ≥ 0 the data polling interval, in milliseconds. Shorter time improve the response of the system, but increase the load on the CPU of both HSYCO and the Tecnoalarm system