Dea Xensity

From HSYCO
Jump to navigation Jump to search

DEA XENSITY is a Point ID intrusion detection system using special piezoelectric sensors for the protection of doors, windows, glass surfaces, security grilles and walls. This driver is compatible with the following controllers: Xensity128, Xensity64, Xensity32. Make sure to install the latest available firmware.

Communication

DEA XENSITY panels can be connected via ethernet. A valid IP address must be assigned to the controller using the configuration software.

Note  In case of multiple DEA XENSITY IO Servers running on the same HSYCO Server you must assign a different UDP port to each XENSITY driver

HSYCO Configuration

Add a XENSITY I/O Server in the I/O Servers section of the Settings and set its parameters:

Communication

  • Address: IP address of the XENSITY controller (mandatory)
  • Port: UDP port (mandatory)

High Availability

  • Shutdown when inactive: defaults to false.

Options

ID Default Values Description
startupevents false true generate IO events also during the driver’s start-up phase
false start generating events only after HSYCO is aligned with the current status of the system
pollinterval 1000 n ≥ 0 the data polling interval, in milliseconds. Shorter time improve the response of the system, but increase the load on the CPU of both HSYCO and the Xensity system

Datapoints

ID Value R/W Description
connection online R connection established
offline R HSYCO can't connect to the panel
alarm 0 R no alarms
1 R at least one zone of this controller on alarm
link.x16 0 R Connection with X16-ER16L is not stable
1 R Connection with X16-ER16L is stable
link.sens 0 R Connection with sensors is not stable
1 R Connection with sensors is stable
bus.power 0 R Bus sensors power supply not ok
1 R Bus sensors power supply ok
alarm.nf 0 R panel in not in test mode
1 R At least one alarm is active - not filtered-
global.daynight 0 R panel in day mode
1 R panel is night mode
global.mcpalarm 0 R mcp alarm off
1 R mcp alarm on
global.sounder.delay.enabled 0 R sounders delay disabled
1 R sounders delay enabled
global.sounder.delay.in.progress 0 R sounders delay not in progress
1 R sounders delay in progress
global.sounder.outputs.activated 0 R sounders outputs not active
1 R sounders outputs active
global.sounder.outputs.silenced 0 R sounders outputs not silenced
1 R sounders outputs silenced
global.sounder.disabled 0 R sounders are enabled
1 R sounders are disabled
global.sounder.override.time.elapsed 0 R override sounders time is not elapsed
1 R ovveride sounders time elapsed
global.sounder.in.test 0 R sounders not in test
1 R sounders in test
global.fire.routing.delay.enabled 0 R fire routing delay not enabled
1 R fire routing delay enabled
global.fire.routing.delay.in.progress 0 R fire routing delay not in progress
1 R fire routing in progress
global.fire.routing.ouputs.activated 0 R fire routing outputs not activated
1 R fire routing outputs activated
global.fire.routing.ack 0 R fire routing not in ack
1 R fire routing ack
global.fire.routing.disabled 0 R fire routing enabled
1 R fire routing disabled
global.fire.routing.test.on 0 R fire routing test is off
1 R fire routing test on
global.fire.routing.ext.delay.in.progress 0 R fire routing ext delay not in progress
1 R fire routing ext delay in progress
node.<n>.loop.<l>.sensor.<s>.prealarm 0 R not in prealarm
1 R prealarm
node.<n>.loop.<l>.sensor.<s>.alarm 0 R not in alarm
1 R alarm
node.<n>.loop.<l>.sensor.<s>.fault 0 R not in fault
1 R fault
node.<n>.loop.<l>.sensor.<s>.test 0 R not in test
1 R in test
node.<n>.loop.<l>.sensor.<s>.dis 0 R enabled
1 R disabled
node.<n>.loop.<l>.module.<s>.prealarm 0 R not in prealarm
1 R prealarm
node.<n>.loop.<l>.module.<s>.alarm 0 R not in alarm
1 R alarm
node.<n>.loop.<l>.module.<s>.fault 0 R not in fault
1 R fault
node.<n>.loop.<l>.module.<s>.test 0 R not in test
1 R in test
node.<n>.loop.<l>.module.<s>.dis 0 R enabled
1 R disabled

Release Notes

3.7.0

  • initial release


KILSEN is a registered trademark of UTC Climate, Controls & Security