Dea Xensity
DEA XENSITY is a Point ID intrusion detection system using special piezoelectric sensors for the protection of doors, windows, glass surfaces, security grilles and walls. This driver is compatible with the following controllers: Xensity128, Xensity64, Xensity32. Make sure to install the latest available firmware.
Contents
Communication
DEA XENSITY panels can be connected via ethernet. A valid IP address must be assigned to the controller using the configuration software.
In case of multiple DEA XENSITY IO Servers running on the same HSYCO Server you must assign a different UDP port to each XENSITY driver
HSYCO Configuration
Add a XENSITY I/O Server in the I/O Servers section of the Settings and set its parameters:
Communication
- Address: IP address of the XENSITY controller (mandatory)
- Port: UDP port (mandatory)
High Availability
- Shutdown when inactive: defaults to false.
Options
ID | Default | Values | Description |
---|---|---|---|
startupevents | false | true | generate IO events also during the driver’s start-up phase |
false | start generating events only after HSYCO is aligned with the current status of the system | ||
pollinterval | 1000 | n ≥ 0 | the data polling interval, in milliseconds. Shorter time improve the response of the system, but increase the load on the CPU of both HSYCO and the Xensity system |
Datapoints
ID | Value | R/W | Description |
---|---|---|---|
connection | online | R | connection established |
offline | R | HSYCO can't connect to the panel | |
alarm | 0 | R | no alarms |
1 | R | at least one zone of this controller on alarm | |
link.x16 | 0 | R | Connection with X16-ER16L is not stable |
1 | R | Connection with X16-ER16L is stable | |
link.sens | 0 | R | Connection with sensors is not stable |
1 | R | Connection with sensors is stable | |
bus.power | 0 | R | Bus sensors power supply not ok |
1 | R | Bus sensors power supply ok | |
alarm.nf | 0 | R | No alarms |
1 | R | At least one alarm is active - not filtered- | |
tamper.nf | 0 | R | No tamper alarms |
1 | R | At least one tamper alarm is active - not filtered- | |
arm | 0 | R | arm is not active |
1 | R | arm is active | |
in.tamper | 0 | R | Tamper input is not active |
1 | R | Tamper input is active | |
battery.low | 0 | R | Battery charge ok |
1 | R | Battery charge is low | |
test.fail | 0 | R | Autotest is ok |
1 | R | At least one sensor failed autotest | |
bus.fault | 0 | R | Sensors bus is ok |
1 | R | Sensors bus fault | |
bus.overcurr | 0 | R | Current on sensors bus is ok |
1 | R | Over current on sensors bus | |
tamper | 0 | R | No sensors in tamper alarm |
1 | R | At least one sensor in tamper alarm | |
power.fault | 0 | R | Power ok |
1 | R | Power fail | |
vin | <v> | R | Power supply voltage <v> in mV |
oc<n> | 0 | R | Open collector output <n> is open |
1 | R | Open collector output <n> is closed | |
rel<n> | 0 | R | Relay <n> is open |
1 | R | Relay <n> is closed | |
in<n> | 0 | R | Input <n> is open |
1 | R | Input <n> is closed | |
serial | <string> | R | Serial number <string> |
seclev | <n> | R | Global security level <n> |
global.fire.routing.ext.delay.in.progress | 0 | R | fire routing ext delay not in progress |
1 | R | fire routing ext delay in progress | |
node.<n>.loop.<l>.sensor.<s>.prealarm | 0 | R | not in prealarm |
1 | R | prealarm | |
node.<n>.loop.<l>.sensor.<s>.alarm | 0 | R | not in alarm |
1 | R | alarm | |
node.<n>.loop.<l>.sensor.<s>.fault | 0 | R | not in fault |
1 | R | fault | |
node.<n>.loop.<l>.sensor.<s>.test | 0 | R | not in test |
1 | R | in test | |
node.<n>.loop.<l>.sensor.<s>.dis | 0 | R | enabled |
1 | R | disabled | |
node.<n>.loop.<l>.module.<s>.prealarm | 0 | R | not in prealarm |
1 | R | prealarm | |
node.<n>.loop.<l>.module.<s>.alarm | 0 | R | not in alarm |
1 | R | alarm | |
node.<n>.loop.<l>.module.<s>.fault | 0 | R | not in fault |
1 | R | fault | |
node.<n>.loop.<l>.module.<s>.test | 0 | R | not in test |
1 | R | in test | |
node.<n>.loop.<l>.module.<s>.dis | 0 | R | enabled |
1 | R | disabled |
Release Notes
3.7.0
- initial release
KILSEN is a registered trademark of UTC Climate, Controls & Security