Daikinrc

From HSYCO
Jump to navigation Jump to search

The DAIKINRC I/O Server is compatible with the Daikin room air conditioner series CTXM, ATXM and FXTM units that can be fitted with the Daikin wireless LAN adapter (BRP06xxx) and are supported by the Daikin Controller iOS and Android app.

A single DAIKINRC I/O Server controls all the devices connected to the local network.

Daikin Configuration and Discovery

All units must be connected to the same LAN of the HSYCO Server. When the DAIKINRC I/O Server starts, and then periodically every 30 to 60 seconds, a discovery request is sent to the LAN. New units responding to the discovery request will start to be polled by the I/O Server and become online.

HSYCO Configuration

Add a DAIKINRC I/O Server in the I/O Servers section of the Settings and set its parameters.

Note A single DAIKINRC I/O Server discovers and controls all units connected to the LAN.


Communication

As the I/O Server automatically discovers all units connected to the local network, no connection parameters are required.

High Availability

  • Shutdown when inactive: defaults to true.

Options

ID Default Values Description
pollinterval 5 1 <= n <= 30 the status poll interval, in seconds

Datapoints

In the following table, replace <unit> with the name assigned to a room air conditioner unit. The unit name is shown in the Daikin Controller app.

Names are transformed to lowercase. For instance, if the unit name is "DaikinAP44822", the <unit> part of the corresponding data points will be "daikinap44822".

ID Value R/W Description
<unit>.connection online R connection established to the unit
offline R HSYCO can’t connect to the unit (after initial successful discovery)
<unit>.address <a.b.c.d> R the IP address of the unit connected to the local WiFi network. As the address is assigned by the DHCP server, the unit address may change over time
<unit>.fan.direction off R fan blades stay in a fixed position
W stop vertical/horizontal movement of fan blades
h R fan blades swing horizontally
W enable fan blades horizontal swing
v R fan blades swing vertically
W enable fan blades vertical swing
hv R fan blades swing horizontally and vertically
W enable fan blades horizontal and vertical swing
<unit>.fan.rate auto R airflow rate automatic operation
W set automatic airflow rate
silence R airflow rate quiet operation (reduced flow rate, for low noise operation)
W set airflow rate quiet operation
1 ... 5 R airflow rate level
W set airflow rate level (1 is slower, 5 is faster)
<unit>.humidity.current <value> R the current relative humidity level (if supported by the unit and operation mode)
<unit>.humidity.setpoint <value> R the relative humidity set-point
W set the relative humidity set-point (if supported by the unit and operation mode)
up W increase the relative humidity set-point by 10%
down W decrease the relative humidity set-point by 10%
<unit>.mac <a.b.c.d.e.f> R the network interface hardware address of the unit connected to the local WiFi network. The hardware address is fixed
<unit>.mode auto R automatic operation mode
W set automatic operation mode (the unit automatically switches between cooling and heating)
cooling R cooling operation mode
W set cooling operation mode
heating R heating operation mode
W set heating operation mode
dehum R drying operation mode
W set drying operation mode (the unit controls the humidity, not the temperature)
fan R fan operation mode
W set fan operation mode (temperature control disabled)
<unit>.name <name> R the unit name, as shown in the Daikin Controller app
<unit>.power off R the unit is not operating
W turn the unit off
on R the unit is operating
W turn the unit on
flip W turn the unit on if currently off, and off if currently on
<unit>.temp.current <value> R the current room temperature (in °C)
<unit>.temp.outside <value> R the current outside temperature (in °C)
<unit>.temp.setpoint <value> R the temperature set-point (in °C)
W set the temperature set-point (in °C, with .5 degrees accuracy)
up W increase the temperature set-point by 0.5°C
down W decrease the temperature set-point by 0.5°C
<unit>.version <value> R the unit firmware version

User Interface

Daikinrc Object

The user interface for the DAIKINRC I/O Server.

UI Object daikinrc.png

The daikinrc object is listed in the Project Editor’s new object list only when a DAIKINRC I/O Server is defined.


Parameters

  • id: the object's ID, used by UISets
  • server id: the server ID.
  • unit: the room air conditioner unit id. Supports Redirect variables
  • position: the object's position. Use the pixels or rows and columns coordinates format

Syntax

(daikinrc[!<id>] <server id>; <unit>; <position>)

E.g.

(daikinrc d1; daikinap30859; r1c1)

UI Attributes

Common attributes

Name Value Description
pos x<x>y<y> Position specified as x/y coordinates. E.g. x-5y10
visible true Default. Show the object
false Hide the object
blink true | slow Blink the object at a slow speed
fast Blink the object at a fast speed
false Stop the blinking
opacity 0.0 ... 1.0 Object opacity from 0 (not visible) to 1 (fully visible)
rotation 0 ... 360 Object rotation in degrees. Images are rotated around the center point, all other objects are rotated around the top left corner

Release Notes

3.8.0

  • initial release


Daikin is a registered trademarks of Daikin Corp.