The KSENIA lares 4.0 is a multi-area security system. The I/O Server has been tested on unit with firmware version 1.72.2 and web server version 1.32.7. Actually this driver runs only in HTTP mode (port 80 is set by default).


HSYCO Configuration

Add a LARES4 I/O Server in the I/O Servers section of the Settings and set its parameters:

Communication

  • IP Address: host name or IP address of the panel
  • IP Port: leave it blank

Authentication

  • Password: pin to access the web server

High Availability

  • Shutdown when inactive: defaults to false.

Options

ID Default Values Description
startupevents false true generate IO events also during the driver’s start-up phase
false start generating events only after HSYCO is aligned with the current status of the system
pollinterval 1000 n > 1000 the data acquisition interval, in milliseconds
logsize 300 n ≥ 0 the number of log lines to display in the UI object
gui true true enable the UISET "visible" field for all partition zones
false disable the UISET "visible" field for all partition zones


Datapoints

ID Value R/W Description
connection online R connection established
offline R HSYCO can't connect to the panel
p<n>.desc <text> R description of partition <n>
p<n>.armed 0 R partition <n> is disarmed
W disarm partition <n>
1 R partition <n> is armed
W arm partition <n>
p<n>.alarm 0 R partition <n> not in alarm
1 R partition <n> in alarm
p<n>.tamper 0 R partition <n> not in tamper
1 R partition <n> in tamper
z<n>.desc <text> R description of zone <n>
z<n>.alarm 0 R zone <n> not in alarm
1 R zone <n> in alarm
z<n>.mask 0 R zone <n> not masked
1 R zone <n> masked
z<n>.tamper 0 R zone <n> not in tamper
1 R zone <n> in tamper
z<n>.error 0 R zone <n> not in error
1 R zone <n> in error
z<n>.bypass 0 R zone <n> is not bypassed
W unbypass zone <n>
1 R zone <n> is bypassed
W bypass zone <n>
o<n>.desc <text> R description of output <n>
o<n> 0 R output <n> is off
W turn off output <n>
1 R output n <n> is on
W turn on output <n>
voltage.low 0 R system voltage is ok
1 R system voltage is low
batt.low 0 R battery is ok
1 R battery is low
batt.fault 0 R battery is ok
1 R battery fault
pstn.fault 0 R pstn is ok
1 R pstn fault
credit.low 0 R credit is ok
1 R credit is low
system.fault 0 R system is ok
1 R system fault
mobile.fault 0 R mobile is ok
1 R mobile fault
s<n>.desc <text> R description of scenario <n>
s<n> 1 W trigger scenario <n>

User Interface

UISET Actions

ID Attribute Set to
log value latest security log lines (as many as specified by the 'logsize' option)
log0 value latest security log (it will vanish after 5 seconds)
z<n>.tamper visible false zone n not in tampering
true zone n in tampering
z<n>.bypass visible false zone n not bypassed
true zone n bypassed
z<n>.alarm visible false zone n not in alarm
true zone n in alarm
z<n>.error visible false zone n not in error state
true zone n in error state
z<n>.mask visible false zone n not masked
true zone n masked

Log Files

If a Ksenia anti-intrusion unit is connected to HSYCO, the security.log file will be written in the same directories as the daily log files.

This file is never overwritten or deleted from HSYCO SERVER.

2018.02.20 16:59:28.516 - lares - 20/02/2018 16:56:36 - Disinserimento - Part 1 - U1
2018.02.20 17:00:24.527 - lares - 20/02/2018 16:57:36 - Inserimento - Part 1 - U1
2018.02.20 17:00:44.318 - lares - 20/02/2018 16:57:57 - Allarme - Zone 1
2018.02.20 17:00:49.241 - lares - 20/02/2018 16:57:58 - Ripristino - Zone 1
2018.02.20 17:00:54.043 - lares - 20/02/2018 16:58:06 - Disinserimento - Part 1 - U1
2018.02.20 17:01:18.905 - lares - 20/02/2018 16:58:29 - Fallita Comunicazione - Leonardo - Vocale GSM
2018.02.20 17:01:29.053 - lares - 20/02/2018 16:58:40 - Fallita Comunicazione - Leonardo - SMS

Other information about the Ksenia driver are stored in the message.log daily file.

Release Notes

3.8.0

  • initial version release