Difference between revisions of "TLABQ"

From HSYCO
Jump to navigation Jump to search
Line 86: Line 86:
  
 
|rowspan="4" |model
 
|rowspan="4" |model
|stop
+
|Quadrio
 
|rowspan="4" |R
 
|rowspan="4" |R
 
|rowspan="4" |security panel model
 
|rowspan="4" |security panel model
|-
 
|Quadrio
 
 
|-
 
|-
 
|Small
 
|Small

Revision as of 19:15, 1 March 2021

The TLAB-Q is a multi-area security system

HSYCO Configuration

Add the TLABQ I/O Server in the I/O Servers section of the Settings and set its parameters:

Communication

  • IP Address: host name or IP address of the panel
  • IP Port: TCP/IP port assigned to the panel's web server

Authentication

  • User: username to access the web server
  • Password: password to access the web server

Options

ID Default Values Description
startupevents false true generate IO events also during the driver’s start-up phase
false start generating events only after HSYCO is aligned with the current status of the system
gui true true enable the UISET "visible" field for all system zones
false disable the UISET "visible" field for all system zones
pollinterval 1000 n > 1000 the data acquisition interval, in milliseconds
logsize 400 n ≥ 0 the number of log lines to display in the UI object


Datapoints

ID Value R/W Description
connection online R connection established
offline R HSYCO can't connect to the panel
id Q R security panel series identification
model Quadrio R security panel model
Small
Medium
LArge
fw <val> R firmware version running on the security panel
dataconfig 0..999 R data configuration version
accesstype admin R connection established
no_valid_access R HSYCO can't connect to the panel
<user_index> R HSYCO can't connect to the panel
temp <val> R security panel temperature (C°)
credit <val> R SIM credit (€)
gsm.fault 1 R gsm error
0 R no gsm error
gsm.fault.cause 1 R network registration error
2 R no SIM
3 R no service provider
4 R low signal
5 R no response to sent command
6 R SIM pin block
pstn.fault 1 R PSTN fault
0 R no PSTN fault

User Interface

UISET Actions

ID Attribute Set to
log value latest security log lines (as many as specified by the 'logsize' option)
connection.online visible true when datapoint connection = online
false when datapoint connection = offline
connection.offline visible true when datapoint connection = offline
false when datapoint connection = online
<datapoint_id>.1 visible true when datapoint with ID <datapoint_id> has value '1'
false when datapoint with ID <datapoint_id> has value '0'
<datapoint_id>.0 visible true when datapoint with ID <datapoint_id> has value '0'
false when datapoint with ID <datapoint_id> has value '1'

USER Commands

Name Param Action
p<n>.armed 0 disarm partition <n>
1 arm partition <n>
p<n>.armed.part 1 part arm partition <n>
p<n>.reset 1 reset partition <n>
o<n> 0 set PC controlled output <n> off
1 set PC controlled output <n> on
ox<n> 0 set X-10 controlled output <n> off
1 set X-10 controlled output <n> on
key <code> send keypad key (see above for codes)

Release Notes

3.8.0

  • initial release