TLABQ

From HSYCO
Jump to navigation Jump to search

The T-LAB Q is a multi-area security system with four different models; the model Quadrio supports only one area, the models Small, Medium, Large support four areas. Each area is divided into four groups (A,B,C,D). Number of zones and outputs is variable and depend on the model.

HSYCO Configuration

Add the TLABQ I/O Server in the I/O Servers section of the Settings and set its parameters:

Communication

  • IP Address: host name or IP address of the panel
  • IP Port: TCP/IP port assigned to the panel's web server

Authentication

  • User: username to access the web server
  • Password: password to access the web server

Options

ID Default Values Description
startupevents false true generate IO events also during the driver’s start-up phase
false start generating events only after HSYCO is aligned with the current status of the system
gui true true enable the UISET "visible" field for all system zones
false disable the UISET "visible" field for all system zones
pollinterval 1000 n > 1000 the data acquisition interval, in milliseconds
logsize 400 n ≥ 0 the number of log lines to display in the UI object


Datapoints

ID Value R/W Description
connection online R connection established
offline R HSYCO can't connect to the panel
id Q R security panel series identification
model Quadrio R security panel model
Small
Medium
Large
fw <text> R firmware version running on the security panel
dataconfig 0..999 R data configuration version
accesstype admin R the admin accessed the panel
no_valid_access R no valid access to the panel
<user_index> R index of the user that accessed the panel
temp <val> R security panel temperature (C°)
credit <val> R SIM credit (€)
gsm.fault 1 R gsm error detected
0 R no gsm error
gsm.fault.cause 1 R network registration error
2 R no SIM
3 R no service provider
4 R low signal
5 R no response to sent command
6 R SIM pin block
pstn.fault 1 R PSTN fault detected
0 R no PSTN fault
nopower 1 R no power supply
0 R power supply in normal state
nopower.device 65534 R system detected lack of power supply
<n> R index of device that detected lack of power supply
batt.fault 1 R battery fault detected
0 R no battery fault
batt.fault.device 65534 R system detected battery fault
<n> R index of device that detected battery fault
tamper 1 R tamper on a device detected
0 R no tamper detected
tamper.device 65534 R system in tampering
<n> R index of device in tampering
coercion 1 R user coercion detected
0 R no user coercion detected
coercion.user <n> R index of user under duress
radiointerference 1 R radiointerference detected
0 R no radiointerference detected
radiozone.fault 1 R radio zone fault detected
0 R no radio zone fault detected
radiozone.fault.zone <n> R index of radio zone fault
theft 1 R theft detected
0 R no theft detected
theft.device <n> R index of device that detected theft
medemergency 1 R medical emergency detected
0 R no medical emergency detected
medemergency.device <n> R index of device that detected medical emergency
radiohooter.fault 1 R radio hooter fault detected
0 R no radio hooter fault detected
radiohooter.fault.device <n> R index of device that detected radio hooter fault
radiokeyboard.fault 1 R radio keyboard fault detected
0 R no radio keyboard fault detected
radiokeyboard.fault.device <n> R index of device that detected radio keyboard fault
radiohooter.ids <text> R list of radio hooter indexes in tampering
remoteaccess 1 R remote access detected
0 R no remote access detected
a<n>.name <text> R/W name of area <n> (max. 16 characters)
a<n>.ins 0 R/W disarm all groups in area <n>
1 R/W arm all groups in area <n>
a<n>.alarmgroups <text> R list of groups, in area <n>, in alarm state
a<n>.tampergroups <text> R list of groups, in area <n>, in tampering
a<n>.prealarmgroups <text> R list of groups, in area <n>, in pre-alarm state
a<n>.blindgroups <text> R list of groups, in area <n>, in blind state
a<n>.group.<a,b,c,d>.en 0 R group <a,b,c,d> in area <n> is disabled
1 R group <a,b,c,d> in area <n> is enabled
a<n>.group.<a,b,c,d>.ins 0 R/W group <a,b,c,d> in area <n> is disarmed
1 R/W group <a,b,c,d> in area <n> is armed
a<n>.group.<a,b,c,d>.name <text> R/W name of group <a,b,c,d> in area <n> (max. 16 characters)
totaloutputs <n> R total outputs number associated to the security panel
totalradiooutputs <n> R total radio outputs number associated to the security panel
o<n>.status 0 R output n doesn't exist
1 R output n not configured and disabled
2 R output n not configured and enabled
11 R output n configured and disabled
12 R output n configured and enabled
o<n> 0 W disable output n
1 W enable output n
o<n>.name <text> W change name of output n (max. 16 characters)
o<n>.sec 0 W remove timing on output n
<k> W output n will change status (enable/disable) after k seconds
totalwiredzones <n> R total wired zones number
totalradiozones <n> R total radio zones number
z<n>.status 1 R zone n excluded
2 R zone n in normal state
3 R zone n in tampering
11 R zone n open internal contact
12 R zone n open external contact
13 R zone n open internal and external contacts
20 R alarm memory in zone n and all contacts closed
21 R alarm memory in zone n and internal contact open
22 R alarm memory in zone n and external contact open
23 R alarm memory in zone n and all contact open
40 R zone n in alarm and all contacts closed
41 R zone n in alarm and internal contact open
42 R zone n in alarm and all external contact open
43 R zone n in alarm and all contacts open

User Interface

UISET Actions

ID Attribute Set to
log value latest security log lines (as many as specified by the 'logsize' option)
log0 value latest security log (it will vanish after 5 seconds)
z<n>.not.configured visible true zone n is not configured
false zone n is configured
z<n>.excluded visible true zone n is excluded
false zone n is not excluded
z<n>.normal visible true zone n is in normal state
false zone n is not in normal state
z<n>.tamper visible true zone n is in tampering
false zone n is not in tampering
z<n>.open.internal visible true internal contact open in zone n
false not internal contact open in zone n
z<n>.open.external visible true external contact open in zone n
false not external contact open in zone n
z<n>.open.both visible true both contacts open in zone n
false not both contacts open in zone n
z<n>.alarm.memory.closed.both visible true alarm memory in zone n and both contacts closed
false not alarm memory in zone n and both contacts closed
z<n>.alarm.memory.open.internal visible true alarm memory in zone n and internal contact open
false not alarm memory in zone n and internal contact open
z<n>.alarm.memory.open.external visible true alarm memory in zone n and external contact open
false not alarm memory in zone n and external contact open
z<n>.alarm.memory.open.both visible true alarm memory in zone n and both contacts open
false not alarm memory in zone n and both contacts open
z<n>.alarm.closed.both visible true alarm in zone n and both contacts closed
false not alarm in zone n and both contacts closed
z<n>.alarm.open.internal visible true alarm in zone n and internal contact open
false not alarm in zone n and internal contact open
z<n>.alarm.open.external visible true alarm in zone n and external contact open
false not alarm in zone n and external contact open
z<n>.alarm.open.both visible true alarm in zone n and both contacts open
false not alarm in zone n and both contacts open

Log Files

If a TLABQ I/O Server is connected to HSYCO, the security.log file will be written in the same directories as the daily log files.

This file is never overwritten or deleted from HSYCO SERVER.

2021.03.02 10:55:28.470 - tlabq - 02/03/2021 10:50 - armed - remote user - area 1 - groups: A,B
2021.03.02 10:55:28.534 - tlabq - 02/03/2021 10:51 - disarmed - remote user
2021.03.02 10:55:28.555 - tlabq - 02/03/2021 10:51 - armed - remote user - area 1 - groups: A,B
2021.03.02 10:55:28.561 - tlabq - 02/03/2021 10:52 - disarmed - remote user
2021.03.02 10:55:28.568 - tlabq - 02/03/2021 10:52 - armed - remote user - area 1 - groups: A,B
2021.03.02 10:55:28.570 - tlabq - 02/03/2021 10:52 - disarmed - remote user
2021.03.02 10:55:29.504 - tlabq - HSYCO ONLINE
2021.03.02 11:01:28.088 - tlabq - 02/03/2021 11:00 - remote access - 93.51.114.164
2021.03.02 11:30:49.349 - tlabq - HSYCO OFFLINE

Other information about the TLABQ driver are stored in the message.log daily file.

Release Notes

3.8.0

  • initial release


T-LAB is a registered trademarks of T-LAB SRL.