Difference between revisions of "NotifierESibM"

From HSYCO
Jump to navigation Jump to search
 
(9 intermediate revisions by the same user not shown)
Line 392: Line 392:
 
|-
 
|-
  
|rowspan="2" |panel.<p>.line.<l>.sensor.<s>.alarm
+
|rowspan="2" |panel.<pan>.line.<lin>.sensor.<sens>.alarm
 
|0
 
|0
 
|R
 
|R
Line 403: Line 403:
 
|-
 
|-
  
|rowspan="2" |panel.<p>.line.<l>.sensor.<s>.excluded
+
|rowspan="2" |panel.<pan>.line.<lin>.sensor.<sens>.excluded
 
|0
 
|0
 
|R
 
|R
Line 414: Line 414:
 
|-
 
|-
  
|rowspan="2" |panel.<p>.line.<l>.sensor.<s>.fault
+
|rowspan="2" |panel.<pan>.line.<lin>.sensor.<sens>.fault
 
|0
 
|0
 
|R
 
|R
Line 425: Line 425:
 
|-
 
|-
  
|rowspan="2" |panel.<p>.line.<l>.sensor.<s>.normal
+
|rowspan="2" |panel.<pan>.line.<lin>.sensor.<sens>.normal
 
|0
 
|0
 
|R
 
|R
Line 436: Line 436:
 
|-
 
|-
  
|rowspan="2" |panel.<p>.line.<l>.sensor.<s>.not.programmed
+
|rowspan="2" |panel.<pan>.line.<lin>.sensor.<sens>.not.programmed
 
|0
 
|0
 
|R
 
|R
Line 447: Line 447:
 
|-
 
|-
  
|rowspan="2" |panel.<p>.line.<l>.sensor.<s>.test
+
|rowspan="2" |panel.<pan>.line.<lin>.sensor.<sens>.test
 
|0
 
|0
 
|R
 
|R
Line 458: Line 458:
 
|-
 
|-
  
|panel.<p>.line.<l>.sensor.\ls\g.analogval
+
|panel.<pan>.line.<lin>.sensor.<sens>.analogval
 
|0..65535
 
|0..65535
 
|R
 
|R
 
|analog value of the sensor
 
|analog value of the sensor
 
|-
 
|-
 +
 +
|-
 +
 +
|panel.<pan>.line.<lin>.sensor.<sens>.status
 +
|0,1,2,3,4,5
 +
|R
 +
|sensor status numeric value. 0=normal,1=not programmed,2=excluded,3=test,4=alarm,5=fault
 +
|-
 +
 +
|-
 +
 +
|rowspan="2" |panel.<pan>.line.<lin>.sensor.<sens>
 +
|include
 +
|W
 +
|include sensor
 +
|-
 +
|exclude
 +
|W
 +
|exclude sensor
 +
|-
 +
 +
|-
 +
 +
|rowspan="2" |panel.<pan>.line.<lin>.module.<mode>.subaddr.<addr>.active
 +
|0
 +
|R
 +
|module is not active
 +
|-
 +
|1
 +
|R
 +
|module is active
 +
 +
|-
 +
 +
|rowspan="2" |panel.<pan>.line.<lin>.module.<mode>.subaddr.<addr>.excluded
 +
|0
 +
|R
 +
|module is excluded
 +
|-
 +
|1
 +
|R
 +
|module is not excluded
 +
 +
|-
 +
 +
|rowspan="2" |panel.<pan>.line.<lin>.module.<mode>.subaddr.<addr>.fault
 +
|0
 +
|R
 +
|module is not faulty
 +
|-
 +
|1
 +
|R
 +
|module is faulty
 +
 +
|-
 +
 +
|rowspan="2" |panel.<pan>.line.<lin>.module.<mode>.subaddr.<addr>.normal
 +
|0
 +
|R
 +
|module is not in normal mode
 +
|-
 +
|1
 +
|R
 +
|module is in normale mode
 +
 +
|-
 +
 +
|rowspan="2" |panel.<pan>.line.<lin>.module.<mode>.subaddr.<addr>.not.programmed
 +
|0
 +
|R
 +
|module is programmed
 +
|-
 +
|1
 +
|R
 +
|module is not programmed
 +
 +
|-
 +
 +
|rowspan="2" |panel.<pan>.line.<lin>.module.<mode>.subaddr.<addr>.test
 +
|0
 +
|R
 +
|module is not in test
 +
|-
 +
|1
 +
|R
 +
|module is in test
 +
 +
|-
 +
 +
|panel.<pan>.line.<lin>.module.<mode>.subaddr.<addr>.status
 +
|0,1,2,3,4,5
 +
|R
 +
|module status numeric value. 0=normal,1=not programmed,2=excluded,3=test,4=active,5=fault
 +
|-
 +
 +
|-
 +
 +
|rowspan="2" |panel.<pan>.line.<lin>.module.<mode>.subaddr.<addr>
 +
|include
 +
|W
 +
|include module
 +
|-
 +
|exclude
 +
|W
 +
|exclude module
 +
|-
 +
 +
|-
 +
 +
|rowspan="2" |panel.<pan>.line.<lin>.module.<mode>.subaddr.<addr>
 +
|0
 +
|W
 +
|deactivate module
 +
|-
 +
|1
 +
|W
 +
|activate module
 +
|-
 +
 +
|-
 +
 +
 +
|}
 +
 +
=== UISET Actions ===
 +
 +
{| class="wikitable"
 +
!ID
 +
!Attribute
 +
!colspan="2"|Set to
 +
 +
|-
 +
 +
|<datapoint_id>.name
 +
|<String>
 +
|colspan="2"|name assigned to <datapoint_id> has specified in the notifieresibm.ini file
 +
 +
 +
|-
 +
 +
|panel.<pan>.line.<lin>.sensor.<sens>.analogval
 +
|value
 +
|colspan="2"|analog value of panel.<pan>.line.<lin>.sensor.<sens>
 +
 +
 +
|-
 +
 +
|rowspan="2"|connection.label
 +
|rowspan="2"|visible
 +
|true
 +
|when datapoint connection = offline
 +
|-
 +
|false
 +
|when datapoint connection = online
 +
 +
|-
 +
 +
|rowspan="2"|<datapoint_id>.1.label
 +
|rowspan="2"|visible
 +
|true
 +
|when datapoint with ID <datapoint_id> has value '1'
 +
|-
 +
|false
 +
|when datapoint with ID <datapoint_id> has value '0'
 +
 +
|-
 +
 +
|rowspan="2"|<datapoint_id>.0.label
 +
|rowspan="2"|visible
 +
|true
 +
|when datapoint with ID <datapoint_id> has value '0'
 +
|-
 +
|false
 +
|when datapoint with ID <datapoint_id> has value '1'
  
 
|-
 
|-
  
 
|}
 
|}
 +
 +
== Release Notes ==
 +
=== 3.9.0 ===
 +
*initial release
 +
 +
----
 +
 +
 +
''NOTIFIER is a registered trademark of Honeywell International, Inc.''

Latest revision as of 15:15, 30 May 2024

Notifier E-SIB-M is a license key to enable Modbus TCP communication for a series of Notifier and Honeywell fire detection panels:

AM8200 Notifier (legacy up to 8 lines per control panel)
AM8100 Notifier
AM1000CL
AM2000CL
AM6000CL
MA1000-03
MA2000-03
MA1000-01
MA2000-01
MA1000-02
MA2000-02
AM8200N Notifier (up to 4 lines per control panel)
AM8200N Honeywell (up to 4 lines per control panel)
AM8200 Honeywell (legacy up to 8 lines per control panel)
AM8100 Honeywell
MA1000-04 
MA2000-04

The integration with HSYCO can be accomplished via a standard Modbus TCP/IP connection. This I/O server was developed following the MODBUS documentation Mod-Bus_Prot_rev.01.

Note For any information regarding the activation of the Modbus protocol on the E-SIB-M dongle, please contact your Notifier distributor.

Communication

Notifier E-SIB-M compatible panels can be connected via ethernet. A valid IP address must be assigned to the panel. MODBUS PROTOCOL must be enabled. Please refer to the panel manual for detailed instruction about MODBUS protocol configuration.


HSYCO Configuration

Add a Notifieresibm I/O Server in the I/O Servers section of the Settings and set its parameters:

Communication

  • Address: IP address of the Notifier E-SIB-M panel panel
  • Port: TCP/IP port for MODBUS communication (default 502)

High Availability

  • Shutdown when inactive: defaults to false.

Options

ID Default Values Description
gui true true enable support for the UI object, UISET actions and USER commands
false disable UI support
startupevents false true generate IO events also during the driver’s start-up phase
false start generating events only after HSYCO is aligned with the current status of the system
modulesnumber 159 n = 0..159 highest module address of all the connected panels. E.G. If 2 panel with 2 lines are connected and the first panel has 20 modules on the first line, and 10 on the second, and the second panel has 30 modules on the first line and 10 on the second you should set modulesnumber = 30 to read all the modules
sensorsnumber 159 n = 0..159 highest sensor address of all the connected panels. E.G. If 2 panel with 2 lines are connected and the first panel has 30 sensors on the first line, and 10 on the second, and the second panel has 50 sensors on the first line and 10 on the second you should set sensorsnumber = 50 to read all the modules
zonesnumber 10 n = 0..2000 set to the highest zone number configured in the system.

notifieresibm.ini

The notifieresibm.ini file is a specific configuration file located in the root directory.

This file is required to provide the I/O Server the name assignment of zones and devices.

This is an example of the file content:

noti.z1 = Zone 1
noti.panel.1.line.1.sensor.1 = Sensor 1 Line 1 Panel 1
noti.panel.1.line.1.sensor.10 = Sensor 10 Line 1 Panel 1
noti.panel.1.line.1.module.1.subddr.2 = Module 1 Line 1 Panel 1 Subaddr 2
noti.panel.1.line.2.module.1.subddr.1 = Module 1 Line 2 Panel 1 Subaddr 1

Where "noti" is the I/O Server id of the NOTIFIERESIBM I/O Server

If you have multiples NOTIFIERESIBM I/O Servers:

noti1.z1 = Zone 1
noti1.panel.1.line.1.sensor.1 = Sensor 1 Line 1 Panel 1
noti2.panel.1.line.1.sensor.10 = Sensor 10 Line 1 Panel 1
noti2.panel.1.line.1.module.1.subddr.2 = Module 1 Line 1 Panel 1 Subaddr 2
noti3.panel.1.line.2.module.1.subddr.1 = Module 1 Line 2 Panel 1 Subaddr 1

Datapoints

ID Value R/W Description
connection online R connection established
offline R HSYCO can't connect to the panel
command.reset 1 W force panel reset
command.silence 1 W silence panel
command.sirens.toggle 1 W toggle sirens status, if a fire alarm is active
global.alarm.led.faulty 0 R fault led is off
1 R fault led is on
global.alarm.led.faulty.flashing 0 R fault led is not flashing
1 R fault led is flashing
global.alarm.led.status 0 R alarm led is off
1 R alarm led is on
global.evacuation 0 R not in evacuation
1 R evacuation active
global.exclusions.present 0 R no active exclusions
1 R at least on sensor or zone excluded
global.hardware.key.present 0 R the hardware key is not present
1 R the hardware key is present
global.license.missing 0 R license key not missing
1 R license key is missing
global.system.buzzer.status 0 R system buzzers are off
1 R system buzzers are on
global.sounder.outputs.silenced 0 R sounders outputs not silenced
1 R sounders outputs are silenced
global.system.siren.silenced 0 R sirens are not silenced
1 R sirens are silenced
global.system.siren.status 0 R sirens status is off
1 R sirens status is on
global.test.events.presents 0 R system not in test mode
1 R system in test mode
global.lines.number 1..128 R number of lines configured on the system
global.panels.number 1..64 R number of panels configured on the system
global.model <String> R panel model, list of supported panels: am8200,am8100,am1000cl,am2000cl,am6000cl,ma1000-03,ma2000-03,am8200,ma2000-01,ma1000-02,ma2000-02,am8200n,am8200n-honeywell,am8200-honeywell,am8100-honeywell,ma1000-04,ma2000-04
global.zone.<n>.alarm 0 R zone <n> not in alarm
1 R zone <n> in alarm
global.zone.<n>.empty 0 R zone <n> not empty
1 R zone <n> is empty
global.zone.<n>.fault 0 R zone <n> not faulty
1 R zone <n> is faulty
global.zone.<n>.normal 0 R zone <n> not in normal mode
1 R zone <n> is in normal mode
global.zone.<n>.prealarm 0 R zone <n> not in prealarm
1 R zone <n> is in prealarm
global.zone.<n>.status 0,1,3,4,5,6 R zone <n> status in numeric value. 0=normal,1=empty,3=test, 4=alarm,5=fault,6=prealarm
panel.<pan>.line.<lin>.sensor.<sens>.alarm 0 R sensor not in alarm
1 R sensor in alarm
panel.<pan>.line.<lin>.sensor.<sens>.excluded 0 R sensor included
1 R sensor excluded
panel.<pan>.line.<lin>.sensor.<sens>.fault 0 R sensor not faulty
1 R sensor faulty
panel.<pan>.line.<lin>.sensor.<sens>.normal 0 R sensor not in normal mode
1 R sensor in normal mode
panel.<pan>.line.<lin>.sensor.<sens>.not.programmed 0 R sensor is programmed
1 R sensor is not programmed
panel.<pan>.line.<lin>.sensor.<sens>.test 0 R sensor not in test
1 R sensor in test
panel.<pan>.line.<lin>.sensor.<sens>.analogval 0..65535 R analog value of the sensor
panel.<pan>.line.<lin>.sensor.<sens>.status 0,1,2,3,4,5 R sensor status numeric value. 0=normal,1=not programmed,2=excluded,3=test,4=alarm,5=fault
panel.<pan>.line.<lin>.sensor.<sens> include W include sensor
exclude W exclude sensor
panel.<pan>.line.<lin>.module.<mode>.subaddr.<addr>.active 0 R module is not active
1 R module is active
panel.<pan>.line.<lin>.module.<mode>.subaddr.<addr>.excluded 0 R module is excluded
1 R module is not excluded
panel.<pan>.line.<lin>.module.<mode>.subaddr.<addr>.fault 0 R module is not faulty
1 R module is faulty
panel.<pan>.line.<lin>.module.<mode>.subaddr.<addr>.normal 0 R module is not in normal mode
1 R module is in normale mode
panel.<pan>.line.<lin>.module.<mode>.subaddr.<addr>.not.programmed 0 R module is programmed
1 R module is not programmed
panel.<pan>.line.<lin>.module.<mode>.subaddr.<addr>.test 0 R module is not in test
1 R module is in test
panel.<pan>.line.<lin>.module.<mode>.subaddr.<addr>.status 0,1,2,3,4,5 R module status numeric value. 0=normal,1=not programmed,2=excluded,3=test,4=active,5=fault
panel.<pan>.line.<lin>.module.<mode>.subaddr.<addr> include W include module
exclude W exclude module
panel.<pan>.line.<lin>.module.<mode>.subaddr.<addr> 0 W deactivate module
1 W activate module

UISET Actions

ID Attribute Set to
<datapoint_id>.name <String> name assigned to <datapoint_id> has specified in the notifieresibm.ini file


panel.<pan>.line.<lin>.sensor.<sens>.analogval value analog value of panel.<pan>.line.<lin>.sensor.<sens>


connection.label visible true when datapoint connection = offline
false when datapoint connection = online
<datapoint_id>.1.label visible true when datapoint with ID <datapoint_id> has value '1'
false when datapoint with ID <datapoint_id> has value '0'
<datapoint_id>.0.label visible true when datapoint with ID <datapoint_id> has value '0'
false when datapoint with ID <datapoint_id> has value '1'

Release Notes

3.9.0

  • initial release


NOTIFIER is a registered trademark of Honeywell International, Inc.