NotifierESibM
Notifier E-SIB-M is a license key to enable Modbus TCP communication for a series of Notifier and Honeywell fire detection panels:
AM8200 Notifier (legacy up to 8 lines per control panel) AM8100 Notifier AM1000CL AM2000CL AM6000CL MA1000-03 MA2000-03 MA1000-01 MA2000-01 MA1000-02 MA2000-02 AM8200N Notifier (up to 4 lines per control panel) AM8200N Honeywell (up to 4 lines per control panel) AM8200 Honeywell (legacy up to 8 lines per control panel) AM8100 Honeywell MA1000-04 MA2000-04
The integration with HSYCO can be accomplished via a standard Modbus TCP/IP connection. This I/O server was developed following the MODBUS documentation Mod-Bus_Prot_rev.01.
For any information regarding the activation of the Modbus protocol on the E-SIB-M dongle, please contact your Notifier distributor.
Communication
Notifier E-SIB-M compatible panels can be connected via ethernet. A valid IP address must be assigned to the panel. MODBUS PROTOCOL must be enabled. Please refer to the panel manual for detailed instruction about MODBUS protocol configuration.
HSYCO Configuration
Add a Notifieresibm I/O Server in the I/O Servers section of the Settings and set its parameters:
Communication
- Address: IP address of the Notifier E-SIB-M panel panel
- Port: TCP/IP port for MODBUS communication (default 502)
High Availability
- Shutdown when inactive: defaults to false.
Options
ID | Default | Values | Description |
---|---|---|---|
gui | true | true | enable support for the UI object, UISET actions and USER commands |
false | disable UI support | ||
startupevents | false | true | generate IO events also during the driver’s start-up phase |
false | start generating events only after HSYCO is aligned with the current status of the system | ||
unitid | 1 | > 0 | MODBUS unit ID of the INIM PREVIDIA panel |
pollingtime | 1000 | n >= 1000, n <= 30000 | the data polling interval, in milliseconds. |
loopsnumber | 16 | n = 1..16 | the number of configured loops |
groupsnumber | 240 | n = 1..240 | the number of configured groups |
zonesnumber | 1000 | n = 1..1000 | the number of configured zones |
model | ultra | ultra | Inim Previdia Ultra panel |
max | Inim Previdia Max panel | ||
compact | Inim Previdia Compact panel |