Aritech Interlogix FP2000 is a multi-area fire panel. The integration with HSYCO can be accomplished via direct control through the RS232 port on the panel. The FP2000 I/O Server in HSYCO supports the integration of more than one unit within the same HSYCO interface.

Communication

Employ an RS-232 cable to connect the panel directly to HSYCO.

RS-232 parameters:

Baud rate same as panel settings (default 9600)
Data bits 8
Stop bit 1
Parity none
Flow control RTS/CTS


HSYCO Configuration

Options

ID Default Values Description
gui true true enable support for the UI object, UISET actions and USER commands
false disable UI support
startupevents false true generate IO events also during the driver’s start-up phase
false start generating events only after HSYCO is aligned with the current status of the system
accesscode 0 0 do not request for authentication (the I/O Server will only be usable as panel emulator)
1 - 9999 use the specified value as access code for requesting authentication
keypaddisable false true disable the emulator keypad buttons
false the emulator keypad buttons are enabled
controldisable false true disable the emulator control buttons
false the emulator control buttons are enabled
displayhlcolor 339933 000000 - FFFFFF use the specified hexadecimal value as the highlight color for the display of the emulator

Datapoints

ID Value R/W Description
connection online R connection established
offline R HSYCO can't connect to the panel
emulation 1 R emulation is active
W activate emulation
0 R emulation is disabled
W disable emulation
led.general.fire.1

led.general.fire.2
led.general.processor
led.general.supply.fault
led.general.disabled
led.general.fault
led.general.supply
led.general.system.fault
led.brigade.delay.off
led.brigade.delay.on
led.brigade.stop
led.brigade.fault
led.brigade.signal
led.sounder.delay.on
led.sounder.silence
led.sounder.fault
led.sounder.sound
led.sounder.delay.off
led.control.test
led.control.disabled
led.control.silence.buzzer
led.all
led.panel

on R the corresponding LED is on
off R the corresponding LED is off
blink W the corresponding LED is on, blinking
status.alarm.count <num> R count of fires
status.fault.count <num> R count of faults
status.condition.count <num> R count of conditions
status.event.count <num> R count of all the events other than fire, fault or condition
clock <date_time> R the panel’s clock is set to <date_time>. The value has the format "yyyy-mm-dd hh:mm:ss" (e.g. "2012-12-30 16:59:23")
W set the data and time of the panel to <date_time>. The value has the format "yyyy-mm-dd hh:mm:ss" (e.g. "2012-12-30 16:59:23")
read W request for reading date and time set on the panel
l<n>.s<m>.name <name> R reports the name of sensor <m> on loop <n>
l<n>.s<m>.alarm.fire 1 R fire alarm active for sensor <m> on loop <n>
0 R no fire alarm active for sensor <m> on loop <n>
l<n>.s<m>.alarm.communication 1 R fault alarm active for sensor <m> on loop <n>
0 R no fault alarm active for sensor <m> on loop <n>
l<n>.s<m>.alarm.disabled 1 R disabled alarm active for sensor <m> on loop <n>
0 R no disabled alarm active for sensor <m> on loop <n>
l<n>.s<m>.alarm.type 1 R wrong type alarm active for sensor <m> on loop <n>
0 R no wrong type alarm active for sensor <m> on loop <n>
l<n>.s<m>.alarm.address 1 R double address alarm active for sensor <m> on loop <n>
0 R no double address alarm active for sensor <m> on loop <n>
l<n>.s<m>.alarm.condition 1 R pre condition alarm active for sensor <m> on loop <n>
0 R no pre condition alarm active for sensor <m> on loop <n>
l<n>.s<m>.alarm.maintenance 1 R maintenance alarm active for sensor <m> on loop <n>
0 R no maintenance alarm active for sensor <m> on loop <n>
l<n>.s<m>.alarm.notype 1 R no type alarm active for sensor <m> on loop <n>
0 R type alarm active for sensor <m> on loop <n>
l<n>.s<m>.alarm.enabled 1 R enabled alarm active for sensor <m> on loop <n>
0 R no enabled alarm active for sensor <m> on loop <n>
l<n>.s<m>.alarm.twoset 1 R two set alarm active for sensor <m> on loop <n>
0 R no two set alarm active for sensor <m> on loop <n>
l<n>.s<m>.alarm.segment 1 R 7 segment alarm active for sensor <m> on loop <n>
0 R no 7 segment alarm active for sensor <m> on loop <n>
l<n>.s<m>.alarm.led 1 R LED alarm active for sensor <m> on loop <n>
0 R no LED alarm active for sensor <m> on loop <n>
l<n>.s<m>.alarm.segment.cont 1 R 7 segment continuous alarm active for sensor <m> on loop <n>
0 R no 7 segment continuous alarm active for sensor <m> on loop <n>
l<n>.s<m>.alarm.flag 1 R flag alarm active for sensor <m> on loop <n>
0 R no flag alarm active for sensor <m> on loop <n>
l<n>.s<m>.alarm.pending 1 R alarm pending for sensor <m> on loop <n>
0 R no alarm pending for sensor <m> on loop <n>
l<n>.s<m>.alarm 1 R one of the above alarms is active for sensor <m> on loop <n>
0 R none of the above alarms is active for sensor <m> on loop <n>
l<n>.s<m>.alarm.count <num> R reports the number of alarm states been active for sensor <m> on loop <n>
z<n>.name <name> R reports the name of zone <n>
z<n>.alarm.fire 1 R MCP fire alarm active on zone <n>
0 R no MCP fire alarm active on zone <n>
z<n>.alarm.fault 1 R fault alarm active on zone <n>
0 R no fault alarm active on zone <n>
z<n>.alarm.coincidence 1 R coincidence alarm active on zone <n>
0 R no coincidence fire alarm active on zone <n>
z<n>.alarm.isolated 1 R isolated alarm active on zone <n>
0 R no isolated alarm active on zone <n>