Redirect variables

From HSYCO
Jump to navigation Jump to search

Redirect variables allow UI Objects to be linked dynamically to a source.

Redirect variables can be used in:

  • any object's id
  • I/O Server Objects, in server id and address parameters
  • Button objects, in the address parameter


Syntax

Variables are defined with the following syntax:

[<variable name>]

E.g.

[myaddr]

Setting Values

Server UISets (from events or java) are used to set a redirect variable's value. Each redirect variable is a property of the "redirect" object. For example, a redirect variable called "myaddr" can be set to "70" with a UISet command on events:

UISET redirect.myaddr=70

Example: Userlist object (redirecting the object's ID)

In this example we use a single UserList object to display different values associated with distinct IDs. In a project we place a UserList and two User buttons. We use a redirect variable as the ID: myid. We leave parameters and labels empty, to be set by UISets.

Redirect vars 03.png

Each User button will have "changeid" as name and "ulist1" or "ulist2" respectively as param.

In events we add:

# initialize two UserList objects with different values
init : {
    uiSet("ulist1", "parameters", "1,2,3");
    uiSet("ulist1", "labels", "one,two,three");
    uiSet("ulist2", "parameters", "a,b,c");
    uiSet("ulist2", "labels", "A,B,C");
}
# change the id to show different lists
function userCommand(session, userid, name, param) : {
    if (name == "changeid") {
        uiSet("redirect", "myid", param);
    }
}

The parameters and labels for ulist1 and ulist2 will be initialized. Clicking on a button in the interface will execute the above callback, which sets the redirect variables' values and changes the ID of the UserList object accordingly, which will in turn display one of the two sets of values.

Example: TempMini Object

In this example we will use a single TempMini object to display different sources. In hsyco.ini we have an ioServer with 3 zones.

ioServers = bmne500
ioServersType.bmne500 = MYHOME
ioServersOptions.bmne500 = tempzones=1;2;3

In a project we place a TempMini and three User buttons. On the TempMini parameters, we use two redirect variables: mysid and myzone.

Redirect vars 01.png

Each User button will have "changetemp" as name and "1", "2" or "3" respectively as param.

In events we declare:

function userCommand(session, userid, name, param) : {
   if (name == "changetemp") {
	uiSet("redirect", "mysid", "bmne500");
	uiSet("redirect", "myzone", param); // address: "temp."+ myzone
       return "ok";
   }
}

Clicking on a button in the interface will execute the above callback, which sets the redirect variables' values and changes the source of the TempMini object accordingly.

Example: Button object

Similarly to the previous example, in a project we place a Button object with a redirect variable called myaddr. We also place two User buttons with name "changeaddr" and param "light.1" and "autom.1"

Redirect vars 02.png

function userCommand(session, userid, name, param) : {
   if (name == "changeaddr") {
       uiSet("redirect", "myaddr", "dummy."+param); // dummy.light.1
   }
}