[[File:IO Server Avigilon 5.png|center|400px]] | [[File:IO Server Avigilon 5.png|center|400px]] | ||
+ | |||
+ | |||
In this example HSYCO is using the following format: | In this example HSYCO is using the following format: | ||
− | # | + | # |
− | dummyalarm.z24.open=0 | + | dummyalarm.z24.open=0 |
− | * | + | * |
Where "dummyalarm.z24.open" is a datapoint, "0" its value | Where "dummyalarm.z24.open" is a datapoint, "0" its value | ||
+ | |||
+ | Now it is possible to setup Transaction Exceptions, for example to trigger a recording when a zone is alarmed. | ||
+ | |||
+ | [[File:IO Server Avigilon 6.png|center|400px]] | ||
+ | |||
+ | [[File:IO Server Avigilon 7.png|center|400px]] | ||
+ | |||
+ | [[File:IO Server Avigilon 8.png|center|400px]] | ||
+ | |||
+ | [[File:IO Server Avigilon 9.png|center|400px]] | ||
+ | |||
+ | {{tip|The object URL could be used to show an HSYCO interface inside ACC7}} | ||
+ | |||
+ | [[File:IO Server Avigilon 10.png|center|700px]] | ||
+ | |||
+ | [[File:IO Server Avigilon 11.png|center|400px]] | ||
== HSYCO Configuration == | == HSYCO Configuration == | ||
Line 44: | Line 62: | ||
*'''Shutdown when inactive''': defaults to false. | *'''Shutdown when inactive''': defaults to false. | ||
+ | == Datapoints == | ||
+ | |||
+ | {| class="wikitable" | ||
+ | !ID | ||
+ | !Value | ||
+ | !R/W | ||
+ | !Description | ||
+ | |- | ||
+ | |||
+ | |rowspan="2" |connection | ||
+ | |online | ||
+ | |R | ||
+ | |HSYCO connection socket is open | ||
+ | |- | ||
+ | |offline | ||
+ | |R | ||
+ | |HSYCO cannot create the connection socket | ||
+ | |- | ||
+ | |||
+ | |write | ||
+ | |value | ||
+ | |W | ||
+ | |write the message <value> on the connection socket | ||
+ | |- | ||
+ | |} | ||
+ | |||
+ | You can send simple events, by writing a plain text message to the write datapoint, for example: | ||
+ | |||
+ | <pre> | ||
+ | |||
+ | init : { | ||
+ | |||
+ | if (typeof String.prototype.startsWith != 'function') { | ||
+ | String.prototype.startsWith = function (str){ | ||
+ | return this.indexOf(str) == 0;}; | ||
+ | } | ||
+ | } | ||
+ | |||
+ | function IOEvent(name, value) : { | ||
+ | |||
+ | if (name.startsWith("dummyalarm.z")){ | ||
+ | var message = "#\n" + name + "=" + value + "\n*"; | ||
+ | ioSet("avi.write", message); | ||
+ | } | ||
+ | |||
+ | } | ||
+ | </pre> | ||
+ | |||
+ | This code writes on the Avigilon I/O server "avi" a message everytime a datapoint starting with "dummyalarm" change its value. The syntax of the message it the same described in the Communication section. | ||
+ | |||
+ | # | ||
+ | dummyalarm.z24.open=0 | ||
+ | * | ||
== Release Notes == | == Release Notes == |
Latest revision as of 10:46, 20 January 2021
Avigilon Control Center (ACC) 7 is a video management software that can be integrated in HSYCO with a TCP/IP connection. The current release of the I/O Server has been tested with the Avigilon Control Center 7.6.0.22
This driver supports only a single connection with an Avigilon Control Server. If you have multiple Avigilon Control Servers it is mandatory to add more I/O servers to HSYCO, one for each Avigilon Control Server. Every I/O server must use a different TCP/IP port.
Contents
Communication
Here's an example of how to configure Avigilon Control Center to get a message from HSYCO and trigger an action.
Select POS Trasanction in the Advanced configuration menu
Set the transaction source device to the IP address of HSYCO and TCP/IP port specified in the I/O Server declaration (e.g. 10001)
Edit the Transaction Source Data Format
Configure data format as follows
In this example HSYCO is using the following format:
# dummyalarm.z24.open=0 *
Where "dummyalarm.z24.open" is a datapoint, "0" its value
Now it is possible to setup Transaction Exceptions, for example to trigger a recording when a zone is alarmed.
The object URL could be used to show an HSYCO interface inside ACC7
HSYCO Configuration
Add an AVIGILON I/O Server in the I/O Servers section of the Settings and set its parameters:
Communication
- IP Address: IP address of the AVIGILON ACC 7 server. Set to 0.0.0.0 to allow any remote IP address to connect.
- IP Port: TCP/IP port to use, leave blank to use default port 10001
High Availability
- Shutdown when inactive: defaults to false.
Datapoints
ID | Value | R/W | Description |
---|---|---|---|
connection | online | R | HSYCO connection socket is open |
offline | R | HSYCO cannot create the connection socket | |
write | value | W | write the message <value> on the connection socket |
You can send simple events, by writing a plain text message to the write datapoint, for example:
init : { if (typeof String.prototype.startsWith != 'function') { String.prototype.startsWith = function (str){ return this.indexOf(str) == 0;}; } } function IOEvent(name, value) : { if (name.startsWith("dummyalarm.z")){ var message = "#\n" + name + "=" + value + "\n*"; ioSet("avi.write", message); } }
This code writes on the Avigilon I/O server "avi" a message everytime a datapoint starting with "dummyalarm" change its value. The syntax of the message it the same described in the Communication section.
# dummyalarm.z24.open=0 *
Release Notes
3.7.0
- initial release
AVIGILON is a registered trademark of Avigilon Corporation