Difference between revisions of "Tecnofire"
Line 10: | Line 10: | ||
== HSYCO Configuration == | == HSYCO Configuration == | ||
− | Add a | + | Add a TECNOFIRE I/O Server in the [[Settings#I/O Servers|I/O Servers section of the Settings]] and set its parameters: |
=== Communication === | === Communication === | ||
− | *'''IP Address''': the | + | *'''IP Address''': the Tecnofire TFNET interface address |
− | *'''IP Port''': TCP/IP port | + | *'''IP Port''': TCP/IP port assigned to the TECNO OUT protocol. |
=== High Availability === | === High Availability === | ||
Line 20: | Line 20: | ||
− | {{tip|The code | + | {{tip|The code parameter in Options is actually mandatory. The I/O Server cannot start without this parameter.}} |
=== Options === | === Options === |
Revision as of 10:36, 7 February 2017
The Tecnofire TFA1-298,TFA2-569 and TFA4-1192 are advanced, fire detection systems.
Panel's firmware version 1.3.17 or above is required. TFNET firmware version 1.0.02 or above is required.
The integration with HSYCO is based on a TCP/IP network connection.
Contents
HSYCO Configuration
Add a TECNOFIRE I/O Server in the I/O Servers section of the Settings and set its parameters:
Communication
- IP Address: the Tecnofire TFNET interface address
- IP Port: TCP/IP port assigned to the TECNO OUT protocol.
High Availability
- Shutdown when inactive: defaults to true.
The code parameter in Options is actually mandatory. The I/O Server cannot start without this parameter.
Options
ID | Default | Values | Description |
---|---|---|---|
code | code | the user code that the driver uses when sending commands to the Tecnoalarm system. It must be a valid user code, or the MASTER code when using the TP8-64BUS | |
model | string | the system’s model. Use one of the following values: TP16-256, TP8-64BUS, TP8-96VIDEO, TP8-96GSM, TP16-512GSM, TP8-88, TP20-440 | |
startupevents | false | true | generate IO events also during the driver’s start-up phase |
false | start generating events only after HSYCO is aligned with the current status of the system | ||
gui | true | true | enable support of the tecnoalarm Web interface object |
false | disable support of the tecnoalarm Web interface object | ||
userlogs | false | true | generates logs that can be viewed with the userlist object, and can be selected to generate user events |
false | logs for userlist objects disabled. Normal text logs are generated even when this option is false | ||
logsize | 50 | n ≥ 0 | the number of log events shown in the tecnoalarm Web object. Set to 0 to hide the log in the tecnoalarm object |
pass | string | the passphrase used to encrypt the TCP/IP traffic. If the Tecnoalarm system doesn’t support the passphrase, you should omit this parameter | |
polltime | 1000 | n ≥ 0 | the data polling interval, in milliseconds. Shorter time improve the response of the system, but increase the load on the CPU of both HSYCO and the Tecnoalarm system |
Datapoints
ID | Value | R/W | Description |
---|---|---|---|
connection | online | R | connection established |
offline | R | connection failed | |
system.standby | 1 | R | general system stand-by status |
0 | R | reset | |
system.fault | 1 | R | general system fault (low battery or no AC power) |
0 | R | reset | |
system.lowbattery | 1 | R | general low battery fault |
0 | R | reset | |
system.nopower | 1 | R | general no AC power fault |
0 | R | reset | |
system.tamper | 1 | R | general tamper condition (central unit, zones, modules, modules loss of connection) |
0 | R | reset | |
system.radiofault | 1 | R | general radio modules fault |
0 | R | reset | |
system.duress | 1 | R | duress status |
0 | R | reset | |
system.techzone | 1 | R | general technical zones open status |
0 | R | reset | |
system.normal | 1 | R | normal status (AC power ok, battery ok, all zones closed, no tamper) |
0 | R | reset | |
system.maintenance | 1 | R | maintenance mode |
0 | R | reset | |
system.panic | 1 | R | panic alarm |
0 | R | reset | |
system.indoorsiren | 1 | R | general status of indoor sirens |
0 | R | reset | |
system.outdoorsiren | 1 | R | general status of outdoor sirens |
0 | R | reset | |
zone.<n>.excluded | 1 | R | zone <n> disabled |
0 | R | zone <n> enabled | |
zone.<n>.alarm | 1 | R | zone <n> alarm |
0 | R | reset | |
zone.<n>.cablecutstatus | 1 | R | zone <n> cable cut |
0 | R | reset | |
zone.<n>.cablecutalarm | 1 | R | zone <n> cable cut alarm |
0 | R | reset | |
zone.<n>.lowbattery | 1 | R | zone <n> low battery |
0 | R | reset | |
zone.<n>.noradio | 1 | R | zone <n> radio supervision lost |
0 | R | reset | |
zone.<n>.active | 1 | R | zone <n> active |
0 | R | reset | |
zone.<n>.radiolearned | 1 | R | zone <n> radio learned |
0 | R | zone <n> radio not learned | |
zone.<n> | enable | W | sends a zone <n> enable command using default code |
disable | W | sends a zone <n> disable command using default code | |
enable.C | W | sends a zone <n> enable command using code C | |
disable.C | W | sends a zone <n> disable command using code C | |
program.<n>.status | off | R | program <n> reset |
preout | R | program <n> pre out status | |
out | R | program <n> out status | |
armed | R | program <n> armed | |
outpartial | R | program <n> out partial status | |
armedpartial | R | program <n> armed partial | |
endpartial | R | program <n> end of partial | |
program.<n>.prealarm | 1 | R | program <n> pre-alarm |
0 | R | reset | |
program.<n>.alarm | 1 | R | program <n> alarm |
0 | R | reset | |
program.<n>.alarmmemory | 1 | R | program <n> alarm memory |
0 | R | reset | |
program.<n> | arm | W | sends a program <n> arm command using default code |
disarm | W | sends a program <n> disarm command using default code | |
partial | W | sends a program <n> partial arm command using default code | |
full | W | sends a program <n> full arm command using default code | |
arm.<C> | W | sends a program <n> arm command using code <C> | |
disarm.<C> | W | sends a program <n> disarm command using code <C> | |
partial.<C> | W | sends a program <n> partial arm command using code <C> | |
full.<C> | W | sends a program <n> full arm command using code <C> | |
output.<n>.status | 1 | R | output line <n> on |
0 | R | output line <n> off | |
output.<n> | 1 | W | sends an output <n> on command using default code |
on | |||
0 | W | sends an output <n> off command using default code | |
off | |||
1.<C> | W | sends an output <n> on command using code <C> | |
on.<C> | |||
0.<C> | W | sends an output <n> off command using code <C> | |
off.<C> |
User Interface
Tecnoalarm Object
The user interface for the Tecnoalarm multi-area intrusion detection system:
The Tecnoalarm object is listed in the Project Editor’s new object list only when at least one Tecnoalarm I/O Server is defined.
Parameters
- server id: the server ID. Supports Redirect variables
- position: the object's position. Use the pixels or rows and columns coordinates format
Syntax
(tecnoalarm <server id>; <position>)
E.g.
(tecnoalarm serverid; x10y20)
UISET Actions
ID | Attribute | Set to | |
---|---|---|---|
connection.label.online | visible | true when the panel is connected to HSYCO, false otherwise | |
connection.label.offline | visible | true when the panel is not connected, false otherwise | |
program.<n>.status.label.off | visible | true when program <n> is off | |
program.<n>.status.label.preout | visible | true when program <n> is in pre out status, false otherwise | |
program.<n>.status.label.out | visible | true when program <n> is in out status, false otherwise | |
program.<n>.status.label.armed | visible | true when program <n> is armed, false otherwise | |
program.<n>.status.label.outpartial | visible | true when program <n> is in out partial status, false otherwise | |
program.<n>.status.label.armedpartial | visible | true when program <n> is partial armed, false otherwise | |
program.<n>.alarm.label | visible | true when program <n> alarm is active, false otherwise | |
zone.<n>.excluded.label | visible | true when zone <n> excluded, false otherwise | |
zone.<n>.alarm.label | visible | true when zone <n> alarm is active, false otherwise | |
zone.<n>.cablecut.label | visible | true when zone <n> cable cut detected (status or alarm), false otherwise | |
zone.<n>.lowbattery.label | visible | true when zone <n> has low battery, false otherwise | |
zone.<n>.noradio.label | visible | true when zone <n> radio supervision lost, false otherwise | |
zone.<n>.active.label | visible | true when zone <n> is active, false otherwise | |
lock.label | visible | true when the system is armed, false otherwise | |
alarm.label | visible | true when the alarm is active, false otherwise | |
tamper.label | visible | true when a tamper alarm is active, false otherwise |
Log Files
A permanent record of all the events shown in the log page is saved in a file called security.log in the logs/YYYY directory for the current year.
This file is never overwritten or deleted by HSYCO.
2014.07.02 17:56:19.188 - tecno - 02/07/10 17:57:29 Activate Remote 6 Monitor 2014.07.02 17:56:22.211 - tecno - 02/07/10 17:57:32 Deactivate Remote 6 Monitor 2014.07.02 17:56:48.174 - tecno - 02/07/10 17:57:58 Access Remote Master Keyboard 2014.07.02 19:00:06.825 - tecno - 02/07/10 19:01:16 Access Remote Master Keyboardd 2014.07.07 17:07:41.871 - tecno - 07/07/10 17:09:31 Activate Remote 6 Monitor 2014.07.07 17:07:43.669 - tecno - 07/07/10 17:09:32 Deactivate Remote 6 Monitor
Other information related to the Tecnoalarm Tecno Out driver are saved in the daily message.log files.
Release Notes
3.5.0
- added support for TP20-440
3.4.0
- output.N command data point not working
- fixed a bug that caused HSYCO to crash when the code and/or model mandatory parameters were not defined
- user codes starting with one or more zeroes didn't work
- fixed a bug that could prevent reading of the zones status of the TP 8-88 panel
3.3.0
- added support for TP8-88
- Tecnoalarm Tecno Out driver converted to I/O Server
- Java API write command methods are now obsolete and deprecated, replaced by IO write commands
- new (tecnoalarm) object
- new option persistentconnection = <true|false>. If true (default is false) the I/O Server will not periodically disconnect and reconnect (periodic disconnection is used to avoid performance degradation on some firmware versions)
- new option userlogs. Used to create (userlist) clickable logs
3.2.1
- Tecno Out: workaround to address a performance issue on Tecno Out introduced with firmware 1.2.07
2.0.0
- full integration within HSYCO 2.9.0
1.1.4
- fixed a bug affecting the TCP/IP communication when using a passphrase
Tecnoalarm is a registered trademarks of Tecnoalarm srl.