Difference between revisions of "Texecom"
(Created page with "The Texecom Premier Elite control panels are advanced, multi-area security systems. The integration with HSYCO can be accomplished via RS-232 serial communication or via Ether...") |
|||
Line 579: | Line 579: | ||
|- | |- | ||
− | + | |rowspan="2"|connection.online | |
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |rowspan="2"|connection. | ||
|rowspan="2"|visible | |rowspan="2"|visible | ||
|true | |true | ||
− | |||
− | |||
− | |||
|when datapoint connection = online | |when datapoint connection = online | ||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
|- | |- | ||
|false | |false | ||
− | |when | + | |when datapoint connection = offline |
|- | |- | ||
− | |rowspan="2"| | + | |rowspan="2"|connection.offline |
|rowspan="2"|visible | |rowspan="2"|visible | ||
|true | |true | ||
− | |when | + | |when datapoint connection = offline |
|- | |- | ||
|false | |false | ||
− | |when | + | |when datapoint connection = online |
|- | |- | ||
− | + | |rowspan="2"|<datapoint_id>.1 | |
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |rowspan="2"|<datapoint_id> | ||
|rowspan="2"|visible | |rowspan="2"|visible | ||
|true | |true | ||
Line 701: | Line 609: | ||
|- | |- | ||
− | |rowspan="2"|<datapoint_id> | + | |rowspan="2"|<datapoint_id>.0 |
|rowspan="2"|visible | |rowspan="2"|visible | ||
|true | |true | ||
Line 708: | Line 616: | ||
|false | |false | ||
|when datapoint with ID <datapoint_id> has value '1' | |when datapoint with ID <datapoint_id> has value '1' | ||
+ | |||
|} | |} | ||
Revision as of 15:02, 29 June 2017
The Texecom Premier Elite control panels are advanced, multi-area security systems. The integration with HSYCO can be accomplished via RS-232 serial communication or via Ethernet connection.
This I/O Server has been tested with firmware version V3.02.00LS2.
Contents
Communication
RS-232 parameters:
Baud rate | 19200 |
Data bits | 8 |
Stop bit | 2 |
Parity | none |
Flow control | none |
HSYCO Configuration
Add a TEXECOM I/O Server in the I/O Servers section of the Settings and set its parameters:
Communication
- Comm ID: select the comm port the device is connected to.
High Availability
- Shutdown when inactive: defaults to true.
Options
ID | Default | Values | Description |
---|---|---|---|
startupevents | false | true | generate IO events also during the driver’s start-up phase |
false | start generating events only after HSYCO is aligned with the current status of the system | ||
logsize | 20 | n ≥ 0 | the number of log lines to display in the UI object |
pollinterval | 3 | n > 0 | the data acquisition interval, in seconds |
maxzone | 256 | n > 0 | highest zone number among the ones used on the panel |
maxpartition | 16 | n > 0 | highest partition number among the ones used on the panel |
pinlength | 4 | n > 0 | length of the user pins |
Datapoints
ID | Value | R/W | Description |
---|---|---|---|
connection | online | R | connection established |
offline | R | HSYCO can't connect to the panel | |
armed | 0 | R | all areas are disarmed |
1 | R | at least one area is armed
| |
a<n>.armed | 0 | R | area <n> is disarmed |
W | disarm area <n> | ||
away | R | area <n> is armed in “away” mode | |
W | arm area <n> in “away” mode | ||
stay | R | area <n> is armed in “stay” mode | |
W | arm area <n> in “stay” mode | ||
inst | R | area <n> is armed in “instantaneous” mode | |
W | arm area <n> in “instantaneous” mode | ||
a<n>.alarm | 0 | R | no active alarm on area <n> |
1 | R | alarm on area <n> | |
a<n>.tamper | 0 | R | no tamper alarm on area <n> |
1 | R | tamper alarm on area <n> | |
a<n>.alarm.mem | 0 | R | no alarm in memory for area <n> |
1 | R | alarm in memory for area <n> | |
a<n>.tamper.mem | 0 | R | no tamper alarm in memory for area <n> |
1 | R | tamper alarm in memory for area <n> | |
a<n>.auto | 0 | R | auto-arming disabled on area <n> |
1 | R | auto-arming enabled on area <n> | |
a<n>.reset | 1 | W | reset alarms on area <n> |
z<n>.state z<n>d.state |
closed | R | zone <n> (base or double) is closed |
open | R | zone <n> (base or double) is open | |
tamper | R | zone <n> (base or double) is tampered | |
short | R | zone <n> (base or double) is in short circuit | |
z<n>.bypassed z<n>d.bypassed |
0 | R | zone <n> is not bypassed |
W | unbypass zone <n> | ||
1 | R | zone <n> is bypassed | |
W | bypass zone <n> | ||
z<n>.test z<n>d.test |
0 | R | zone <n> is not in test |
1 | R | zone <n> is being tested | |
z<n>.alarm.mem z<n>d.alarm.mem |
0 | R | no alarm in memory for zone <n> |
1 | R | alarm in memory for zone <n> | |
z<n>.tamper.mem z<n>d.tamper.mem |
0 | R | no terminal tamper alarm in memory for zone <n> |
1 | R | terminal tamper alarm in memory for zone <n> | |
or | 0 | R | the relay output on the panel is not active |
W | deactivate the relay output on the panel | ||
1 | R | the relay output on the panel is active | |
W | activate the relay output on the panel | ||
oc1 | 0 | R | the open collector 1 on the panel is not active |
W | deactivate the open collector 1 on the panel | ||
1 | R | the open collector 1 on the panel is active | |
W | activate the open collector 1 on the panel | ||
oc2 | 0 | R | the open collector 2 on the panel is not active |
W | deactivate the open collector 2 on the panel | ||
1 | R | the open collector 2 on the panel is active | |
W | activate the open collector 2 on the panel | ||
o<n> (if defined in hesa.ini) |
0 | R | output <n> is not active |
W | deactivate output <n> | ||
1 | R | output <n> is active | |
W | activate output <n> | ||
fault.fuse.zones | 0 | R | zones fuse OK |
1 | R | fault on zones fuse | |
fault.fuse.ibus | 0 | R | IBUS fuse OK |
1 | R | fault on IBUS fuse | |
fault.battery | 0 | R | battery OK |
1 | R | fault on battery | |
fault.mains | 0 | R | mains OK |
1 | R | panel mains fault | |
fault.phone | 0 | R | phone line OK |
1 | R | fault on phone line | |
fault.jamming | 0 | R | no jamming |
1 | R | radio jamming | |
fault.radio.battery | 0 | R | radio zones battery OK |
1 | R | low battery on radio zone(s) | |
fault.radio.loss | 0 | R | radio zones OK |
1 | R | loss of radio zone(s) | |
battery.volts | <val> | R | the voltage value of the battery is <val> Volts |
tamper.panel | 0 | R | panel OK |
1 | R | panel tampered | |
tamper.cover | 0 | R | panel cover OK |
1 | R | panel cover tampered | |
tamper.reader | 0 | R | readers OK |
1 | R | reader(s) tampered | |
tamper.keypad | 0 | R | keypads OK |
1 | R | keypad(s) tampered | |
tamper.expander | 0 | R | FLEX5 expanders OK |
1 | R | FLEX5 expander(s) tampered | |
reset | 0 | R | communication BUS ready |
1 | R | ongoing reset procedure on communication BUS | |
internet | 0 | R | “internet access” option disabled |
1 | R | “internet access” option enabled | |
service | 0 | R | service jumper in “RUN” position |
1 | R | service jumper in “SERV” position (maintenance) | |
program | 0 | R | panel not in programming mode |
1 | R | ongoing programming via keyboard | |
voice | 0 | R | no SmartLogos30M voice card detected |
1 | R | SmartLogos30M voice card detected |
User Interface
Hesa Object
The user interface for the control and supervision of one area of the system, the zones and the visualization of the security log:
The Hesa object is listed in the Project Editor’s new object list only when at least one HESA I/O Server is defined.
Parameters
- id - the id assigned to the HESA I/O Server in hsyco.ini. Supports Redirect variables
- area - the number of the area to be addressed. Supports Redirect variables
- pos - the object’s position. Use the pixels or rows and columns coordinates format.
Syntax
(hesa <server id>; <area>; <position>)
E.g.
(hesa serverid; area; x10y20)
UISET Actions
ID | Attribute | Set to | |
---|---|---|---|
log | value | latest security log lines (as many as specified by the 'logsize' option) | |
connection.online | visible | true | when datapoint connection = online |
false | when datapoint connection = offline | ||
connection.offline | visible | true | when datapoint connection = offline |
false | when datapoint connection = online | ||
<datapoint_id>.1 | visible | true | when datapoint with ID <datapoint_id> has value '1' |
false | when datapoint with ID <datapoint_id> has value '0' | ||
<datapoint_id>.0 | visible | true | when datapoint with ID <datapoint_id> has value '0' |
false | when datapoint with ID <datapoint_id> has value '1' |
USER Commands
Name | Param | Action |
---|---|---|
a<n>.armed | 0 | disarm area <n> |
stay | arm area <n> in "stay" mode | |
away | arm area <n> in "away" mode | |
inst | arm area <n> in "instantaneous" mode | |
a<n>.reset | 1 | reset alarms on area <n> |
z<n>.bypassed z<n>d.bypassed |
0 | unbypass zone <n> (base or double) |
1 | bypass zone <n> (base or double) | |
or | 0 | deactivate the relay output on the panel |
1 | activate the relay output on the panel | |
oc1 | 0 | deactivate the open collector 1 on the panel |
1 | activate the open collector 1 on the panel | |
oc2 | 0 | deactivate the open collector 2 on the panel |
1 | activate the open collector 2 on the panel | |
o<n> | 0 | deactivate output <n> |
1 | activate output <n> |
To perform any of the above operations it is necessary to enter the user code first. To enter the user code through the user interface use user buttons to create a virtual keypad and assign them name and param values according to this table:
Name | Param | Action |
---|---|---|
digit | {0 ... 9} | append the specified digit to the entered user code |
c | delete the last entered digit |
To visualize the number of entered digits use up to 6 text objects (depending on the number of digits used for user codes) and set their IDs to:
ID | Description |
---|---|
pin.<n> (0 ≤ <n> ≤ 5) |
shows the character '*' when the corresponding digit has been entered, shows '_' otherwise |
The entered code will be cleared after a short period of inactivity.
Log Files
A permanent detailed record of all the Hesa log messages is saved in a file called security.log in the logs/YYYY directory for the current year. This file is never overwritten or deleted by HSYCO.
Other information related to the TEXECOM I/O Server are saved in the daily message.log files.
Release Notes
3.6.0
- initial release
Texecom is a registered trademark of Texecom Ltd.