Bentel

From HSYCO
Revision as of 15:42, 18 February 2014 by Hsyco (talk | contribs) (→‎Log Files)
Jump to navigation Jump to search

The Bentel KYO320 is an advanced, multi-area security system integrated HSYCO.

The KYO320 driver in HSYCO supports the integration of more than one KYO320 unit on the same HSYCO SERVER.

The integration with HSYCO can be accomplished through the standard RS-232 port on the KYO320’s motherboard.

Communication

Employ a DE-9 (often called DB-9) female-female RS-232 crossed cable to connect the RS-232 KYO port to the serial port on HSYCO SERVER. The cable must follow this pinout diagram:

2 ↔ 3
3 ↔ 2
5 ↔ 5

RS-232 parameters:

Baud rate same as defined on the KYO320 (usually 9600, 38400 or 57600)
Data bits 8
Stop bit 1
Parity even
Flow control none


HSYCO Configuration

Options

ID Default Values Description
gui true true enable support for the UI object, UISET actions and USER commands
false disable UI support
language system language en language of log and display messages. Supported values are it and en
it
zoneactivitylog false true logs the open/close status of zones in the log page and security.log files
false disable zone status log
code the user code to be used when sending IO commands to the KYO, if code is not explicitly set in the command
logsize 50 n ≥ 0 the number of log lines to display in the UI object
polltime 1000 n ≥ 0 the data polling interval, in milliseconds. Shorter time improve the response of the system, but increase the load on the CPU of both HSYCO and the KYO system

bentel.ini

The bentel.ini file is an optional configuration file located in the main directory (same directory as hsyco.ini or hsyco.jar) and used to define zones and partitions names. If defined, these names will be used instead of the original numbers in the log files and the bentel GUI object.

The bentel.ini is automatically detected at start-up. Changes to this file become effective when the I/O Server is restarted.

For each zone or partition, enter a line formatted as:

<io_server_id>.zone.<n> = <name>
<io_server_id>.area.<n> = <name>

For instance:

kyo.zone.1 = kitchen
kyo.zone.2 = garage
kyo.area.1 = basement
kyo.area.2 = second floor

Datapoints

ID Value R/W Description
connection online R connection established
offline R HSYCO can't connect to the panel
system.fault 1 R general system fault
0 R reset
system.batteryfault 1 R general battery fault
0 R reset
system.lowbattery 1 R low battery
0 R reset
system.nobattery 1 R low battery
0 R reset
system.nopower 1 R general no AC power fault
0 R reset
system.tamper 1 R general tamper condition (central unit, zones, modules)
0 R reset
system.radiofault 1 R general radio modules fault
0 R reset
system.radiolowbattery 1 R radio modules low battery
0 R reset
system.duress 1 R duress status
0 R reset
system.maintenance 1 R maintenance mode
0 R reset
zone.<n>.disabled 1 R zone <n> disabled
0 R zone <n> enabled
zone.<n>.alarm 1 R zone <n> alarm
0 R reset
zone.<n>.tamper 1 R zone <n> tamper alarm
0 R reset
zone.<n> enable W enable zone <n> using default code
disable W disable zone <n> using default code
enable.<c> W enable zone <n> using code <c>
disable.<c> W disable zone <n> using code <c>
partition.<n>.armed 1 R area <n> is armed (any mode)
0 R reset
partition.<n>.disarmed 1 R area <n> is not armed
0 R reset
partition.<n>.away 1 R area <n> away mode
0 R reset
partition.<n>.stay 1 R area <n> stay mode
0 R reset
partition.<n>.staynodelay 1 R area <n> stay no delay mode
0 R reset
partition.<n>.alarm 1 R area <n> alarm memory
0 R reset
partition.<n> away W arm area <n> using default code
disarm W disarm area <n> using default code
stay W stay arm area <n> using default code
staynodelay W instant stay arm area <n> using default code
away.<c> W arm area <n> using code <c>
disarm.<c> W disarm area <n> using code <c>
stay.<c> W stay arm area <n> using code <c>
staynodelay.<c> W instant stay arm area <n> using code <c>
out.<n> off W turn off output <n> using default code
on W turn on output <n> using default code
off.<c> W turn off output <n> using code <c>
on.<c> W turn on output <n> using code <c>

User Interface

Bentel Object

The user interface for the Bentel KYO320 multi-area intrusion detection system:

UI Object bentel1.png UI Object bentel2.png UI Object bentel3.png UI Object bentel4.png

The Bentel object is listed in the Project Editor’s new object list only when at least one Bentel I/O Server is defined.

Parameters

  • server id: the server ID. Supports Redirect variables
  • position: the object's position. Use the pixels or rows and columns coordinates format

Syntax

(bentel <server id>; <position>)

E.g.

(bentel serverid; x10y20)

UISET Actions

You can use any object that accepts a text attribute, usually text, but also marquee and others, to display the status of the system according to the following table:

USER Commands

ID Attribute Set to
Name Param Action

Log Files

A permanent record of all the events shown in the log page is saved in a file called security.log in the logs/YYYY directory for the current year.

This file is never overwritten or deleted by HSYCO.

2014.07.30 20:09:21.760 - SECOND FLOOR - ARMED
2014.07.30 20:09:21.763 - SECOND FLOOR - AWAY
2014.07.30 20:10:02.364 - [2] GARAGE - OPEN
2014.07.30 20:10:04.779 - [2] GARAGE - OK
2014.07.30 20:10:06.167 - BASEMENT - ALARM
2014.07.30 20:10:48.477 - BASEMENT - DISARMED
2014.07.30 20:10:48.481 - SECOND FLOOR - DISARMED
2014.07.30 20:39:31.326 - ZONE 281 - OPEN
2014.07.30 20:39:36.708 - ZONE 281 - OK
2014.07.30 20:40:41.571 - AC POWER - FAULT
2014.07.30 20:49:58.945 - ZONE 281 - OPEN
2014.07.30 20:50:04.181 - ZONE 281 - OK
2014.07.30 20:50:11.559 - AC POWER - OK

Other information related to the Bentel KYO driver are saved in the daily message.log files.

Release Notes

3.3.0

  • Bentel KIO driver converted to I/O Server
  • Java API write command methods are now obsolete and deprecated, replaced by IO write commands
  • new (bentel) object

2.0.0

  • full integration within HSYCO 2.9.0

1.1.0

  • change to the status polling thread to improve recovery time after transient communication problems


Bentel, KYO and KYO320 are registered trademarks of BENTEL SECURITY SRL.