LoRaWAN

From HSYCO
Jump to navigation Jump to search

The LoRaWAN I/O Server implements both a LoRaWAN Network and Application servers for the integration of a LoRaWAN network.

HSYCO acts as a server for one or more LoRaWAN gateways configured as standard Semtech packet forwarders. Communication is carried on UDP packets.

The implementation complies with the Semtech's paket forwarder protocol v4.0.1 and supports Class A end devices using unconfirmed data frames and ABP authentication.


HSYCO Configuration

Add a LORAWAN I/O Server in the I/O Servers section of the Settings and set its parameters:

Note that only one instance of the LORAWAN I/O Server is allowed and it consumes one item for each defined gateway from the I/O Servers license total.


High Availability

  • Shutdown when inactive: defaults to true.

Options

ID Default Values Description
localport <port_number> the IP port number used locally by HSYCO to listen for incoming UDP packets sent by the gateways
debug false true print debugging information to the logs
false don't print debugging information to the logs

LoRaWAN Utility

Use the LoRaWAN Utility to automatically discover gateways and devices and setup the communication and functional parameters.

Gateways Configuration

Configure the gateway(s) as standard Semtech packet forwarder(s). Make sure the network configuration allows for the communication with HSYCO and use HSYCO's IP address and the port number specified in the "localport" option for the network server's configuration.

Datapoints

3.7.0

  • initial release



LoRaWAN is a registered trademark of LoRa Alliance.

Semtech is a registered trademark of Semtech Corporation.