LoRaWAN
The LoRaWAN I/O Server implements both a LoRaWAN Network and Application servers for the integration of a LoRaWAN network.
HSYCO acts as a server for one or more LoRaWAN gateways configured as standard Semtech packet forwarders. Communication is carried on UDP packets.
The implementation complies with the Semtech's paket forwarder protocol v4.0.1 and supports Class A end devices using unconfirmed data frames and ABP authentication.
Contents
HSYCO Configuration
Add a LORAWAN I/O Server in the I/O Servers section of the Settings and set its parameters:
High Availability
- Shutdown when inactive: defaults to true.
Options
ID | Default | Values | Description |
---|---|---|---|
localport | 1700 | <port_number> | the IP port number used locally by HSYCO to listen for incoming UDP packets sent by the gateways |
debug | false | true | print debugging information to the logs |
false | don't print debugging information to the logs |
LoRaWAN Utility
Use the LoRaWAN Utility to automatically discover gateways and devices and setup the communication and functional parameters.
Gateways Configuration
The LoRaWAN gateway(s) that will be used need to be configured to forward the received device data frames to HSYCO.
To this end, configure the gateway(s) as standard Semtech packet forwarder(s). Make sure the network configuration allows for the communication with HSYCO and use HSYCO's IP address and the port number specified in the "localport" option for the network server's configuration.
Datapoints
ID | Value | R/W | Description |
---|---|---|---|
connection | online | R | ready to receive packets |
offline | R | not ready | |
gw.<id>.lastseen | <ts> | R | timestamp of the last packet received from gateway <id> |
gw.<id>.lastpull | <ts> | R | timestamp of the last "pull data" packet received from gateway <id> |
gw.<id>.stat.time | <time> | R | UTC system time reported in the latest status message from gateway <id> |
gw.<id>.stat.lati | <n> | R | GPS latitude in degree (float, N is +) reported in the latest status message from gateway <id> |
gw.<id>.stat.long | <n> | R | GPS longitude in degree (float, E is +) reported in the latest status message from gateway <id> |
gw.<id>.stat.alti | <n> | R | GPS altitude in meter reported in the latest status message from gateway <id> |
gw.<id>.stat.rxnb | <n> | R | number of radio packets received reported in the latest status message from gateway <id> |
gw.<id>.stat.rxok | <n> | R | number of radio packets received with a valid PHY CRC reported in the latest status message from gateway <id> |
gw.<id>.stat.rxfw | <n> | R | number of radio packets forwarded reported in the latest status message from gateway <id> |
gw.<id>.stat.ackr | <n> | R | percentage of upstream datagrams that were acknowledged reported in the latest status message from gateway <id> |
gw.<id>.stat.dwnb | <n> | R | number of downlink datagrams received reported in the latest status message from gateway <id> |
gw.<id>.stat.txnb | <n> | R | number of packets emitted reported in the latest status message from gateway <id> |
dev.<id>.lastseen | <ts> | R | timestamp of the last packet received from device <id> |
dev.<id>.data | <bytes> | R | Hexadecimal representation of the data transmitted in the last valid packet received from device <id>. E.g.: "010fbb" |
dev.<id>.data.ch<n> | <val> | R | Cayenne channel <n>'s value. Possible values depend on the channel's type, refer to #Cayenne LLP format for details. Datapoint available only if Cayenne data format is enabled on this device |
dev.<id>.data.ch<n>.type | <t> | R | Cayenne channel <n>'s type. Refer to #Cayenne LLP format for details. Datapoint available only if Cayenne data format is enabled on this device |
W | Set Cayenne channel <n>'s type. To be used to write output channels for which no data has been received. Possible values are "1" (digital output) or "3" (analog output). Datapoint available only if Cayenne data format is enabled on this device | ||
dev.<id>.fcnt.up | <n> | R | server-side uplink frame counter for device <id>. Used for frames validation. If never set and no frame has ever been received it is set to -1 |
W | set the server-side downlink frame counter for device <id> | ||
dev.<id>.fcnt.down | <n> | R | value of the last frame counter used to send a downlink to device <id>. If never set o no frame has ever been sent it is set to -1 |
W | set the downlink frame counter for device <id> | ||
dev.<id>.datr | SF<sf>BW<bw> | R | Data rate of last valid packet received from device <id>. <sf> ranges from 7 to 12 and <bw> is either 125, 250 or 500. E.g.: "SF7BW125" |
dev.<id>.codr | <cr> | R | Coding rate of last valid packet received from device <id>. Possible <cr> values: "4/5", "4/6", "4/7", "4/8" |
dev.<id>.freq | <fr> | R | TX central frequency in MHz (float, Hz precision) of last valid packet received from device <id> |
dev.<id>.lsnr | <val> | R | LoRa SNR ratio in dB (float, 0.1 dB precision) of last valid packet received from device <id> |
dev.<id>.rssi | <val> | R | RSSI in dBm (signed integer, 1 dB precision) of last valid packet received from device <id> |
dev.<id>.tmst | <val> | R | gateway internal timestamp of the instant the last valid frame from device <id> was received |
dev.<id>.gw | <gw_id> | R | ID of the gateway from which the latest packet from device <id> was received |
dev.<id>.warning.data | 0 | R | the latest uplink frame from device <id> has been decoded correctly |
1 | R | error decoding the latest uplink frame from device <id> | |
dev.<id>.warning.fcnt | 0 | R | the frame counter in the latest uplink frame from device <id> was valid |
n >= 10 | R | the frame counter in the latest uplink frame from device <id> was not valid (n = 10: repetition) | |
dev.<id>.warning.mic | 0 | R | the message integrity code (MIC) in the latest uplink frame from device <id> was valid |
1 | R | the message integrity code (MIC) in the latest uplink frame from device <id> was not valid | |
dev.<id>.queue | <data> | W | add a frame with the specified data (hexadecimal representation, e.g. "010fbb") to the downlink queue of device <id>, using the default transmission parameters. |
<JSON> | W | add a frame with the specified data and transmission parameters to the downlink queue of device <id>. See #Downlink frame JSON format for details | |
clear | W | clear the downlink queue of device <id> | |
dev.<id>.queue.ch<n> | <val> | W | add a frame to the downlink queue of device <id> with Cayenne-encoded data for setting channel <n> to <val>. Possible values depend on the channel's type. Make sure the channel's type is set before writing this datapoint. The packet will be sent using the default transmission parameters. Datapoint available only if Cayenne data format is enabled on this device |
dev.<id>.queue.size | <n> | R | number of downlink frames in the device's queue |
dev.<id>.error.tx | NONE | R | last downlink for device <id> was sent correctly to the gateway |
<err_code> | R | the gateway responded with the reported error code to the last downlink request for device <id>. Possible values are "TOO_LATE", "TOO_EARLY", "COLLISION_PACKET", "COLLISION_BEACON", "TX_FREQ", "TX_POWER", "GPS_UNLOCKED" | |
dev.<id>.error.data | 0 | R | data in the last frame received from device <id> was processed correctly. Datapoint available only if Cayenne data format is enabled on this device |
1 | R | error processing data in the last frame received from device <id>. Datapoint available only if Cayenne data format is enabled on this device |
Downlink frame JSON format
Datapoint "dev.<id>.queue" accepts as value a JSON object with the following attributes:
- data: hexadecimal representation of the data
- channel: Cayenne channel
- value: value for the specified Cayenne channel
- port: port number to send the data to
- attempts: number of attempts made to deliver the frame to the gateway before discarding it
- txpk: JSON object with the metadata fields to include in the downlink packet:
- codr: Coding rate
- datr: Data rate
- powe: Power
- rfch: RF chain
- For additional fields see here
The attribute "data" or both "channel" and "value" are mandatory; if "data" is specified, "channel" and "value" are ignored. All other attributes are optional. When not specified, default values will be used based on the device's settings and on the latest received packet.
Example 1 (spaces added for readability):
{ "data": "aa330b", "port": 7, "attempts": 5, "txpk" : { "codr": "4/5", "powe": 14, "datr": "SF7BW125", "rfch":0 } }
Example 2:
{ "data": "020304aa330bff", "port": 5 }
Example 3:
{ "channel": 6, "value": 23.14, "attempts": 2 }
Cayenne LLP format
Type value | Type description | Value format |
---|---|---|
0 | digital input | 0 or 1 |
1 | digital output | 0 or 1 |
2 | analog input | signed decimal number with 0.01 resolution |
3 | analog output | signed decimal number with 0.01 resolution |
101 | illuminance sensor | integer value in Lux |
102 | presence sensor | 0 or 1 |
103 | temperature sensor | signed decimal value in °C with 0.1 resolution |
104 | humidity sensor | unsigned decimal value in % with 0.5 resolution |
113 | accelerometer | [x, y, z] where x, y and z represent the acceleration on each axis. They are signed decimal values in G with 0.001 resolution |
115 | barometer | unsigned decimal value in hPa with 0.1 resolution |
134 | gyrometer | [x, y, z] where x, y and z represent the rotation on each axis. They are signed decimal values in °/s with 0.01 resolution |
136 | GPS location | [latitude, longitude, altitude] where latitude and longitude are signed decimal values in ° with 0.0001 resolution and altitude is a signed decimal value in meters with 0.01 resolution |
Release Notes
3.7.0
- initial release
LoRaWAN is a registered trademark of LoRa Alliance.