EL.MO. ETR panels are multi-area intrusion detection systems. The integration with HSYCO can be accomplished via direct control through the RS232 port on the panel.
Contents
Communication
Employ the RS-232 cable provided with the EL.MO. panel to connect it directly to HSYCO or to an Ethernet/RS-232 gateway.
RS-232 parameters:
Baud rate | 9600 |
Data bits | 8 |
Stop bit | 1 |
Parity | none |
Flow control | none |
EL.MO. Configuration
For the newer "G2" series of EL.MO. ETR panels it is necessary to enable the compatibility mode for direct connection in the panel configuration. Refer to its manual for further details.
HSYCO Configuration
Options
ID | Default | Values | Description |
---|---|---|---|
gui | true | true | enable support for the UI object, UISET actions and USER commands |
false | disable UI support | ||
startupevents | false | true | generate IO events also during the driver’s start-up phase |
false | start generating events only after HSYCO is aligned with the current status of the system | ||
offlinelogs | true | false | at startup request the log of all the events occurred while HSYCO was disconnected from the panel |
false | log only events occurred while HSYCO was connected to the panel | ||
pollinterval | 1 | n > 0 | the data acquisition interval, in seconds |
logsize | 20 | n ≥ 0 | the number of log lines to display in the UI object |
Datapoints
ID | Value | R/W | Description |
---|---|---|---|
connection | online | R | connection established |
offline | R | HSYCO can't connect to the panel | |
armed | 1 | R | at least one partition is armed |
W | arm all active areas | ||
0 | R | no partition is armed | |
W | disarm all active areas | ||
armed.max | 1 | R | at least one partition is armed in "max security" mode |
W | arm all active areas in "max security" mode | ||
0 | R | no partition is armed in "max security" mode | |
W | disarm all active areas in "max security" mode | ||
alarm | 1 | R | alarm state active |
0 | R | no active alarm | |
tamper | 1 | R | tamper alarm active |
0 | R | no active tamper alarm | |
i<n>.name | <text> | R | the name of input <n> is set to <text> |
i<n>.open | 1 | R | input <n> open |
0 | R | input <n> closed | |
i<n>.alarm | 1 | R | alarm on input <n> |
0 | R | no alarm on input <n> | |
i<n>.tamper | 1 | R | tamper alarm on input <n> |
0 | R | no tamper alarm on input <n> | |
i<n>.bypassed | 1 | R | input <n> bypassed |
W | bypass input <n> | ||
0 | R | input <n> enabled | |
W | enable input <n> | ||
o<n> | 1 | R | output <n> active |
W | activate output <n> | ||
0 | R | output <n> inactive | |
W | deactivate output <n> | ||
a<n>.<m>.name | <text> | R | the name of partition <m> of area <n> is set to <text> |
a<n>.armed | 1 | W | arm all partitions of area <n> |
0 | W | disarm all partitions of area <n> | |
a<n>.armed.max | 1 | W | arm all partitions of area <n> in "max security" mode |
0 | W | disarm all partitions of area <n> in "max security" mode | |
a<n>.<m>.armed | 1 | R | partition <m> of area <n> is armed |
W | arm partition <m> of area <n> | ||
0 | R | partition <m> of area <n> is disarmed | |
W | disarm partition <m> of area <n> | ||
a<n>.<m>.armed.max | 1 | R | partition <m> of area <n> is armed in "max security" mode |
W | arm partition <m> of area <n> in "max security" mode | ||
0 | R | partition <m> of area <n> is not armed in "max security" mode | |
W | disarm partition <m> of area <n> in "max security" mode | ||
usr<n>.name | <text> | R | the name of user <n> is set to <text> |
kp<n>.tamper | 1 | R | keypad <n> tampered |
0 | R | keypad <n> not tampered | |
fault.battery | 1 | R | battery fault active |
0 | R | no battery fault active | |
panel.tamper | 1 | R | panel tampered |
0 | R | panel not tampered | |
rel.tamper | 1 | R | tamper relay is on |
0 | R | tamper relay is off | |
rel.alarm | 1 | R | alarm relay is on |
0 | R | alarm relay is off |
User Interface
Elmo Object
The user interface for the EL.MO. multi-area intrusion detection system:
The (elmo) object is listed in the Project Editor’s new object list only when at least one EL.MO. I/O Server is defined
Parameters
- server id: the server ID. Supports Redirect variables
- area: the area. Supports Redirect variables
- position: the object's position. Use the pixels or rows and columns coordinates format
Syntax
(elmo <server id>; <area>; <position>)
E.g.
(elmo elm; 1; x10y20)
UISET Actions
ID | Attribute | Set to | |
---|---|---|---|
log | value | latest security log lines (as many as specified by the 'logsize' option) | |
log0 | value | latest line of the security log when a new entry is added, set back to blank after a short period | |
i<n>.name | value | name assigned to input <n> | |
a<n>.<m>.name | value | name assigned to partition <m> of area <n> | |
usr<n>.name | value | name assigned to user <n> | |
connection.label | visible | true | when datapoint connection = offline |
false | when datapoint connection = online | ||
<datapoint_id>.label.1 | visible | true | when datapoint with ID <datapoint_id> has value '1' |
false | when datapoint with ID <datapoint_id> has value '0' | ||
<datapoint_id>.label.0 | visible | true | when datapoint with ID <datapoint_id> has value '0' |
false | when datapoint with ID <datapoint_id> has value '1' |
USER Commands
Name | Param | Action |
---|---|---|
armed | 1 | arm all active areas |
0 | disarm all active areas | |
armed.max | 1 | arm all active areas in "max security" mode |
0 | disarm all active areas in "max security" mode | |
ID.a<n>.armed | 1 | arm all partitions of area <n> |
0 | disarm all partitions of area <n> | |
a<n>.armed.max | 1 | arm all partitions of area <n> in "max security" mode |
0 | disarm all partitions of area <n> in "max security" mode | |
a<n>.<m>.armed | 1 | arm partition <m> of area <n> |
0 | disarm partition <m> of area <n> | |
a<n>.<m>.armed.max | 1 | arm partition <m> of area <n> in "max security" mode |
0 | disarm partition <m> of area <n> in "max security" mode | |
i<n>.bypassed | 1 | bypass input <n> |
0 | enable input <n> | |
o<n> | 1 | activate output <n> |
0 | deactivate output <n> |