Hephais

From HSYCO
Revision as of 10:03, 24 January 2014 by Hsyco (talk | contribs) (→‎Datapoints)
Jump to navigation Jump to search

The SD3 HEPHAIS 1600 is a multi-zones fire panel. The integration with HSYCO can be accomplished via a standard Modbus RTU slave interface. This I/O Server requires HEPHAIS 1600 with protocol modbus JBUS V0.13

Modbus Connections

The HEPHAIS 1600 has a Modbus interface. The default connection parameters are: Modbus address: 1 (can be set to 1 - 247) communication parameters: 9600 bps, 8 bits, 1 stop bit, no parity. Refer to the HEPHAIS 1600 manuals for installation, wiring and power supply requirements.

The modbus wires terminal is the “Block 11”. Modbus type is RS-422/JBUS (IN+/OUT+, IN-/OUT-, GND).

The Modbus-TCP/IP gateway used for the connection must support RS-422/JBUS.

HSYCO Configuration

Options

ID Default Values Description
gui true true enable support for the UI object, UISET actions and USER commands
false disable UI support
startupevents false true generate IO events also during the driver’s start-up phase
false start generating events only after HSYCO is aligned with the current status of the system
address 1 1...247 the panel's Modbus address
pollinterval 3 n > 0 the data acquisition interval, in seconds
maxpoint m4.l2.200 point id id of the highest point used on the panel. The number after ‘m’ represents the number of the module, the number after ‘l’ represents the loop number of the module and the last number is the address of the point within the loop. Acceptable values range from “m1.l1.1” to “m9.l2.200”
hysteresis 0 <n> if different than zero, the datapoints’ values are checked <n> times before being set. Setting this option to a value different from zero will decrease the responsiveness of the driver

hephais.ini

The hephais.ini file is a specific configuration file located in the root directory. Here you can define the names of the users so that they will be automatically added to the user interface. Add a new line for each user using this format:

<io_server_id>.m<m>.l<l>.<addr>.name = <name>

Add a new line to specify the zone the point belongs using this format: <io_server_id>.m<m>.l<l>.<addr>.zone = <name>

Add a new line to define the name of a zone using this format: <io_server_id>.z<n>.name = <name>

For instance:

	fire.m1.l1.1.name = Entrance
	fire.m1.l1.1.zone = 1
	fire.m1.l1.2.name = Corridor
	fire.m1.l1.2.zone = 2

	fire.z1.name = Zone 1
	fire.z2.name = Zone 2

Datapoints

ID Value R/W Description
connection online R connection established
offline R HSYCO can't connect to the panel
alarm 1 R fire panel in alarm
0 R no alarm
fault 1 R fire panel fault
0 R no fault
oos 1 R at least one point out of service
0 R no point out of service
test 1 R at least one zone in test mode
0 R no zone in test mode
error.sys 1 R system fault
0 R no system fault
prealarm 1 R fire panel in pre-alarm
0 R no pre-alarm
alarm.tec 1 R fire panel in technical alarm
0 R no technical alarm
sound 1 R H.S. speaker active
0 R H.S. speaker not active
error.com 1 R fire panel communication error
0 R no fire panel communication error
error.battery 1 R fire panel battery error
0 R no fire panel battery error
error.sector 1 R fire panel sector fault
0 R no fire panel sector fault
z<n>.name <text> R name assigned to zone <n>
z<n>.alarm 1 R fire panel in alarm
0 R no alarm
z<n>.oos 1 R fire panel in alarm
0 R no alarm
z<n>.fault 1 R fire panel in alarm
0 R no alarm
z<n>.test 1 R fire panel in alarm
0 R no alarm
m<m>.l<l>.<n>.name <text> R name assigned to point P of module <m> in loop <l>
m<m>.l<l>.<n>.oos 1 R fire panel in alarm
0 R no alarm
m<m>.l<l>.<n>.alarm 1 R fire panel in alarm
0 R no alarm
m<m>.l<l>.<n>.fault 1 R fire panel in alarm
0 R no alarm
m<m>.l<l>.<n>.alarm.test 1 R fire panel in alarm
0 R no alarm

User Interface

CSx75 Object

The user interface for the Aritech CSx75 multi-area security system.

CSx75 UI Object 1.png CSx75 UI Object 2.png CSx75 UI Object 3.png

The CSx75 object is listed in the Project Editor’s new object list only when at least one Aritech CSx75 I/O Server is defined.

Parameters

  • server id: the server ID. Supports Redirect variables
  • partition: partition number of the Aritech CSx75 multi-area security system. Supports Redirect variables
  • position: the object's position. Use the pixels or rows and columns coordinates format

Syntax

(csx75 <server id>; <partition>; <position>)

E.g.

(csx75 serverid; partition; x10y20)

UISET Actions

ID Attribute Set to
log value latest security log lines (as many as specified by the 'logsize' option)
log0 value latest line of the security log when a new entry is added, set back to blank after a short period
z<n>.name value name assigned to zone <n> (base or double) or its number if no name is defined
p<n>.last.user value ID of the last user who logged in on partition <n>
user<n>.name value name assigned to user <n>
connection.label visible true when datapoint connection = offline
false when datapoint connection = online
p<n>.armed.0.label visible true when partition <n> is disarmed
false when partition <n> is armed
p<n>.armed.away.label visible true when partition <n> is armed in "away" mode
false when partition <n> is not armed in "away" mode
p<n>.armed.stay.label visible true when partition <n> is armed in "stay" mode
false when partition <n> is not armed in "stay" mode
<datapoint_id>.1.label visible true when datapoint with ID <datapoint_id> has value '1'
false when datapoint with ID <datapoint_id> has value '0'
<datapoint_id>.0.label visible true when datapoint with ID <datapoint_id> has value '0'
false when datapoint with ID <datapoint_id> has value '1'

USER Commands

Name Param Action
armed[Note] 0 disarm all partitions
stay arm all partitions in "stay" mode
away arm all partitions in "away" mode
auto initiate auto-arm on all partitions
p<n>.armed[Note] 0 disarm partition <n>
stay arm partition <n> in "stay" mode
away arm partition <n> in "away" mode
auto initiate auto-arm on partition <n>
p<n>.cancel[Note] 1 issue cancel command on partition <n>
p<n>.buzzer 1 start buzzer on partition <n>
p<n>.exit.silent 1 enable silent exit for this arm cycle on partition <n>
Z<n>.bypassed toggle toggle the bypass status of zone <n>
p<n>.chime.mode toggle toggle chime mode on partition <n>
walk.test[Note] 0 stop walk-test mode
1 start walk-test mode
aux1
p<n>.aux1
1 activate auxiliary function 1
aux2
p<n>.aux2
1 activate auxiliary function 2
panic
p<n>.panic
fire issue the fire panic command
medical issue the medical panic command
police issue the police panic command


smoke
p<n>.smoke
reset smoke detector reset
test
p<n>.test
1 perform test
command restart restarts the driver

Note
To perform this operation it is necessary to enter the user code first. To enter the user code through the user interface use user buttons to create a virtual keypad and assign them name and param values according to this table:

Name Param Action
digit {0 ... 9} append the specified digit to the entered user code
c delete the last entered digit

To visualize the number of entered digits use 4 or 6 text objects (depending on the number of digits used for user codes) and set their IDs to:

ID Description
pin.<n>
(0 ≤ <n> ≤ 5)
shows the character '*' when the corresponding digit has been entered, shows '_' otherwise

The entered code will be cleared after a short period of inactivity.