Difference between revisions of "XGenConnect"

From HSYCO
Jump to navigation Jump to search
Line 72: Line 72:
 
|R
 
|R
 
|HSYCO can't connect to the panel
 
|HSYCO can't connect to the panel
 +
 +
|-
 +
 +
|system.status
 +
|<text>
 +
|R
 +
|a list of system status which is supposed be to displayed on panel main screen
 +
 +
|-
 +
 +
|rowspan="21" |area.<k>.<n>
 +
|0
 +
|W
 +
|turn off area n, of bank k
 +
|-
 +
|1
 +
|W
 +
|turn on area n, of bank k, to the partial level
 +
|-
 +
|2
 +
|W
 +
|turn on area n, of bank k, to the away level
 +
|-
 +
|3
 +
|W
 +
|start or restart the exit delay in area n, of bank k
 +
|-
 +
|4
 +
|W
 +
|mute status but leave armed area n, of bank k
 +
|-
 +
|5
 +
|W
 +
|mute area n, of bank k, which is currently in exit delay
 +
|-
 +
|6
 +
|W
 +
|bypass the group specified by HPD
 +
|-
 +
|7
 +
|W
 +
|manual fire alarm
 +
|-
 +
|8
 +
|W
 +
|manual panic alarm
 +
|-
 +
|9
 +
|W
 +
|manual medical alarm
 +
|-
 +
|10
 +
|W
 +
|global chime on
 +
|-
 +
|11
 +
|W
 +
|global chime off
 +
|-
 +
|12
 +
|W
 +
|start fire siren
 +
|-
 +
|13
 +
|W
 +
|start non-fire siren
 +
|-
 +
|14
 +
|W
 +
|restart auto-arm timer
 +
|-
 +
|15
 +
|W
 +
|turn on area n, of bank k, to the away level and cancel any auto stay level
 +
|-
 +
|16
 +
|W
 +
|turn off area n, of bank k, but chirps siren
 +
|-
 +
|17
 +
|W
 +
|turn on area n, of bank k, to the away level but chirps siren
 +
|-
 +
|18
 +
|W
 +
|turn on area n, of bank k, to the stay level but chirps siren
 +
|-
 +
|19
 +
|W
 +
|turn keypad sound on
 +
|-
 +
|20
 +
|W
 +
|manual silent panic
 +
|-
 +
|21
 +
|W
 +
|manual audible panic
 +
  
 
|}
 
|}
Line 91: Line 190:
  
 
|}
 
|}
 
  
 
== Log Files ==
 
== Log Files ==

Revision as of 16:37, 31 March 2021

The xGen Connect is a multi area anti-intrusion system.

Communication

  • IP Address: host name or IP address of the panel
  • IP Port: TCP/IP port assigned to the panel's web server

Authentication

  • User: username to access the web server
  • Password: password to access the web server

Options

ID Default Values Description
startupevents false true generate IO events also during the driver’s start-up phase
false start generating events only after HSYCO is aligned with the current status of the system
gui true true enable the UISET "visible" field for all system zones
false disable the UISET "visible" field for all system zones
pollinterval 1000 n > 1000 the data acquisition interval, in milliseconds
logsize 300 n ≥ 0 the number of log lines to display in the UI object


Datapoints

ID Value R/W Description
connection online R connection established
offline R HSYCO can't connect to the panel
system.status <text> R a list of system status which is supposed be to displayed on panel main screen
area.<k>.<n> 0 W turn off area n, of bank k
1 W turn on area n, of bank k, to the partial level
2 W turn on area n, of bank k, to the away level
3 W start or restart the exit delay in area n, of bank k
4 W mute status but leave armed area n, of bank k
5 W mute area n, of bank k, which is currently in exit delay
6 W bypass the group specified by HPD
7 W manual fire alarm
8 W manual panic alarm
9 W manual medical alarm
10 W global chime on
11 W global chime off
12 W start fire siren
13 W start non-fire siren
14 W restart auto-arm timer
15 W turn on area n, of bank k, to the away level and cancel any auto stay level
16 W turn off area n, of bank k, but chirps siren
17 W turn on area n, of bank k, to the away level but chirps siren
18 W turn on area n, of bank k, to the stay level but chirps siren
19 W turn keypad sound on
20 W manual silent panic
21 W manual audible panic



UISET Actions

ID Attribute Set to
log value latest security log lines (as many as specified by the 'logsize' option)

Log Files

If a XGenConnect I/O Server is connected to HSYCO, the security.log file will be written in the same directories as the daily log files.

This file is never overwritten or deleted from HSYCO SERVER.

2021.03.31 11:27:06.504 - xgen - HSYCO ONLINE
2021.03.31 11:28:23.954 - xgen - Attiva modalità parziale**  Area 1  User 1  Ora: 11:28:23   Data: 31 Mar 2021
2021.03.31 11:28:23.989 - xgen - Allarme*  Area 1  Ora: 11:28:23   Data: 31 Mar 2021
2021.03.31 11:28:25.733 - xgen - Chiusura recente*  Area 1  User 1  Ora: 11:28:23   Data: 31 Mar 2021
2021.03.31 11:28:25.751 - xgen - Allarme*  Porta ingresso  Area 1  Ora: 11:28:23   Data: 31 Mar 2021
2021.03.31 11:29:23.749 - xgen - Ripristino allarme*  Porta ingresso  Area 1  Ora: 11:29:23   Data: 31 Mar 2021
2021.03.31 11:29:23.772 - xgen - Disattiva modalità parziale**  Area 1  User 1  Ora: 11:29:23   Data: 31 Mar 2021

Other information about the TLABQ driver are stored in the message.log daily file.

Release Notes

3.8.0

  • initial release


Hesa is a registered trademarks of Hesa S.p.A.